2015-07-16 12:37:48PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. CORRECT THE FOLLOWING IN YOUR "GENERAL ELECTRICAL
 NOTES"
 NOTE 7: TO INCLUDE KITCHEN COUNTER RECEPTACLES, OR AS
 DIRECTED BY NEC 210.8 (1-8).
 NOTE 10: ROMEX, AS USED HERE TO REPRESENT A TYPE OF
 CABLE IS INCORRECT. ROMEX IS A BRAND NAME AND NOT A
 TYPE. YOU MAY REFER TO TYPE NM, OR THE HARDER TO FIND
 "NMC" & "NMS".
 NOTE 12: TO INCLUDE BATTERY BACK-UP AND BE
 INTER-CONNECTED.
 NOTE 20: TO READ "AS REQUIRED BY NEC 210.12(B) 2008
 ED." ARC-FAULT PROTECTED EXTENDS BEYOND THE LIVING
 ROOM.
 2. AN ADDITIONAL NOTE IS REQUIRED TO ADDRESS THE
 CEILING LUMINAIRE OUTLETS WHICH ARE TO SUPPORT 50LBS.
 PER NEC 314.27.
 3. IN GOING OVER YOUR SUBMITTED LOAD CALCS, I FOUND THE
 FOLLOWING:
 NEC 210.11(C)(1) REQUIRES TWO SMALL APPLIANCE OUTLETS
 IN ADDITION TO OTHER CIRCUITS. YOU ONLY SHOW ONE.
 YOUR GENERAL LIGHTING LOAD DOES NOT MATCH THE AREA
 INDICATED ELSEWHERE ON THE PLANS.
 YOUR CALCS CALL FOR A 700 WATT MICROWAVE/HOOD COMBO.
 REDO THE ELECTRICAL LOAD CALCS TO MATCH SITE SPECIFIC
 DATA.
 4. THE COMBINATION CO/SMOKE DETECTOR IN THE AREA
 LEADING TO THE MASTER BEDROOM NEEDS TO BE IN THE AREA
 OUTSIDE OF THE ROOM AND NOT IN A SEPARATE ROOM.
 SPECIALLY TAKING INTO ACCOUNT THE LOCATION OF THE
 GARAGE.
 5. IN THE RISER DIAGRAM, INCLUDE THE FOLLOWING:
 THE INTER-SYSTEM BONDING TERMINAL REQUIRED BY NEC
 250.94
 INDICATION TO THE SEALING REQUIREMENTS OF NEC 300.5(G)
 FOR THE UNDERGROUND SERVICE LATERAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  