| Notes |
| Date |
Text |
| 2015-06-08 09:05:47 | 1)THE SCUPPER DIAGRAM IS CONFUSING. THE DIAGRAM SHOWS A | | | NEW STORM DRAIN CONNECTION TO AN EXISTING VERTICAL RAIN | | | WATER LEADER BUT THE SLOPE IS AWAY FROM THE CONNECTION | | | TO THE LEADER . AS DRAWN IT WILL NOT DRAIN INTO THE | | | LEADER. CLARIFY. | | | 2) SCUPPERS SHALL DISCHARGE A MINIMUM OF 1 FOOT FROM | | | THE STRUCTURE SIDEWALL PER 2010 FBC SEC.1503.7. | | | 3)THE LETTER FROM THE ENGINEER NOTES THAT THERE ARE NO | | | RATED ASSEMBLIES BEING REPAIRED, ALTERED OR REPLACED | | | YET THE CONTRACTOR'S PROPOSAL REFERS TO FIRE COLLARS. | | | CLARIFY. SUBMIT TWO COPIES OF DETAILS AND SPECS FOR THE | | | FIRE COLLARS. THE ENGINEER SHALL REVIEW AND APPROVE THE | | | TYPE OF FIRE COLLARS TO BE INSTALLED.WPB AMEND. TO 2010 | | | FBC SEC.107.3.4.1. | | | 4) THE OVERFLOW SCUPPERS SHALL BE INDEPENDENT OF THE | | | PRIMARY SYSTEM PER FPC SEC. 1107.2. INDICATE SUCH ON | | | THE PLANS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|