| 2015-06-08 14:10:02 | 6/8/2015 |
| | PROJECT: EGRET REMODEL |
| | PERMIT#: 15060250 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) SMOKE DETECTORS ARE REQUIRED. WHEN ALTERATIONS, |
| | REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| | ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| | EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| | BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| | NEW DWELLINGS. FBC-RESIDENTIAL 314 AND 315. |
| | |
| | 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 3) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| | NO OTHER OUTLETS. NEC 210.52(C)(3) |
| | |
| | 4) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| | THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. (1) BATHROOMS NEC 210.8 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |