| Plan Review Notes For Permit 15060166 |
| Permit Number |
15060166 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-05 15:07:22 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF | | | THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE | | | INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND | | | ALL OTHER APPLICABLE CODES OR STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | | | | 2) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF | | | THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE | | | AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF | | | WALLS REQUIRES AN EVALUATION. | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | |
|