| 2015-11-23 15:51:17 | 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE. ALL |
| | OTHER ELEMENTS DEPICTED ON THE SITE PLANS HAVE NOT |
| | APPROVED BY ZONING. AS SUCH, THE FOLLOWING ITEMS |
| | REQUIRE SEPARATE PERMIT SUBMITTALS, WITH PLANS, AND |
| | HAVE NOT BEEN REVIEWED AS PART OF THIS PERMIT: |
| | |
| | A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION. |
| | PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS |
| | WHERE THE LANDSCAPE PLAN SHOWS HEDGES AND THE NEW FIRE |
| | HYDRANT ON THE NORTH SIDE OF THE BUILDING IS SHOWN |
| | WHERE TREES ARE SHOWN. NOTE: THE AS-BUILT PLANS WILL |
| | NEED TO BE SUBMITTED TO THE PLANNING DIVISION AS PART |
| | OF A MINOR PLANNED DEVELOPMENT AMENDMENT PRIOR TO THE |
| | C.O. FOR THE GARAGE. |
| | B. IRRIGATION |
| | C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING, |
| | STRIPING, AND SIGNAGE |
| | D. BICYCLE RACKS |
| | E. EXTERIOR SIGNAGE |
| | F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY |
| | G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE |
| | H. GENERATOR AND ENCLOSURE |
| | I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND |
| | SIDEWALKS |
| | J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS - |
| | NOTE: |
| | 1. THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES NOT |
| | COMPLY WITH THE DOWNTOWN STREET LIGHTING REQUIREMENTS - |
| | THE FIXTURE SHALL BE MOUNTED ON TOP OF THE POLE WITH |
| | THE LAMP CENTER AT 17 FEET ABOVE GRADE. THE PHILIPS |
| | LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE APPEARS THAT |
| | IT WOULD COMPLY WITH THE DOWNTOWN REQUIREMENTS. |
| | 2. PLEASE REMEMBER THAT PALM BEACH COUNTY COMMITTED TO |
| | COORDINATING WITH RELATED TO USE THE SAME OR SIMILAR |
| | LIGHT FIXTURES IN THE FLORIDA AVENUE RIGHT-OF-WAY AND |
| | THE ENTRY DRIVE AND PLAZA TO MAINTAIN CONSISTENCY |
| | BETWEEN THE TWO PROJECTS. THE SPECIFIED TYPES DO NOT |
| | APPEAR TO BE CONSISTENT. |
| | 3. THE POLES SHOWN IN THE CITY RIGHT-OF-WAY MAY NOT BE |
| | PERMITTED ON THE SITE LIGHTING PERMIT, BUT RATHER SHALL |
| | BE PERMITTED THROUGH THE ENGINEERING SERVICES DIVISION. |
| | 4. ONE OF THE LIGHT POLES IS LOCATED WITHIN THE FIRE |
| | DEPARTMENT ACCESS DRIVEWAY. |
| | K. WORK WITHIN THE FUTURE STAGING AREA |
| | |
| | 2) SIGN #23 AND SIGN #24 AT STAIRWELLS #3 AND #4 SHALL |
| | INCLUDE THE WORD ?ONLY? AFTER EMERGENCY EGRESS. |
| | |
| | 3) A SIGN SHALL BE ADDED ON EACH FLOOR AT THE STAIRWELL |
| | #2 DOOR DIRECTING PATRONS TO EXIT TO THE CONVENTION |
| | CENTER AT THE ELEVATOR LOBBY. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
| | |