| 2015-09-30 10:14:16 | 2ND REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060144 |
| | 9/30/15 |
| | |
| | 1) SHEET MM701: INDICATE THE DURATION OF OPERATION FOR |
| | THE PRESSURIZATION FANS SF-1 & 2 AFTER DETECTION OF A |
| | FIRE- REFER TO SECTION 909.4.6 FBC-10 BUILDING AND |
| | PROVIDE NOTES TO CLARIFY. |
| | 2) MM110: INDICATE HOW THE BASEMENT LEVEL UTILITY ROOMS |
| | B005 & B006 ARE BEING VENTILATED. SHOW THE MEANS AND |
| | PROVIDE CALCULATIONS- SECTION 401 FBC-10 MECHANICAL. |
| | 3) MM220: PROVIDE VENTILATION CALCULATIONS FOR THE |
| | UTILITY ROOM. PLEASE REFER TO SHEET AE140- THE UTILITY |
| | ROOM IS ALSO FOUND ON FLOOR LEVELS 2,3,4,6, & 8; AND ON |
| | FLOOR LEVELS 1,5, & 7 IT IS LABELED AS AN ELECTRICAL |
| | ROOM . PLEASE SHOW THE MEANS OF VENTILATION FOR ALL OF |
| | THESE ROOMS AND PROVIDE SIZING CALCULATIONS. |
| | 4) MM220 & MM801: PROVIDE INSTALLATION AND SUPPORT |
| | DETAILS FOR THE SF-1 AND SF-2 PRESSURIZATION FANS. |
| | 5) MM801, DETAIL 11: THE HEIGHT OF THE RECIRCULATING |
| | FANS ABOVE THE FINISH FLOORS SHALL BE MINIMUM 8' PER |
| | SECTION 304.6 FBC-10 MECHANICAL. PLEASE CORRECT THE |
| | DETAIL. |
| | 6) MM802, DETAIL 3: THE DETAIL IS INCOMPLETE: PROVIDE |
| | FASTENING DETAILS FOR ATTACHING THE CONDENSERS TO THE |
| | BRACKET AND THE BRACKET TO THE WALL. DETAIL 4- PROVIDE |
| | THE TYPE, SIZE, AND DEPTH OF EMBEDMENT FOR THE |
| | CONDENSER TIE-DOWN ANCHOR BOLTS. PLEASE NOTE: SITE |
| | SPECIFICA WINDLOAD ENGINEERING IS REQUIRED FOR ALL |
| | EXTERIOR APPLIANCE INSTALLATIONS- SECTION 301.12 |
| | /FBC-10 MECHANICAL. |
| | 7) PROVIDE THE SEQUENCE OF OPERATION FOR THE |
| | RECIRCULATION FANS, AND ALL OF THE VARIOUS ROOM EXHAUST |
| | FANS. |
| | 8) DUCTLESS SYSTEM 8 SHOWN IN THE SCHEDULE ON MM601 IS |
| | NOT SHOWN ON THE PLANS- PLEASE INDICATE THE SYSTEM |
| | LOCATION ON THE PLANS. |
| | 9) AC CALCULATIONS WERE NOT PROVIDED FOR AC SYSTEMS 2, |
| | 3, 6, 7, & 8- PLEASE PROVIDE THE CALCULATIONS. |
| | 10) AC SYSTEMS 2, 3, 6, 7 & 8 ARE NOT LISTED IN THE |
| | ENERGY CALCULATION FORM 506-2010- PLEASE PROVIDE THE |
| | COMPLIANCE DATA. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |