| 2015-07-14 14:03:17 | FAILED |
| | |
| | PROVIDE RESPONSES IN WRITING. |
| | |
| | 1) THIS PERMIT IS ONLY FOR THE GARAGE STRUCTURE AND THE |
| | COVERED ENTRY STRUCTURE. ALL OTHER ELEMENTS DEPICTED ON |
| | THE SITE PLANS HAVE NOT APPROVED BY ZONING. AS SUCH, |
| | THE FOLLOWING ITEMS REQUIRE SEPARATE PERMIT SUBMITTALS, |
| | WITH PLANS, AND HAVE NOT BEEN REVIEWED AS PART OF THIS |
| | PERMIT: |
| | |
| | A. LANDSCAPE, TO INCLUDE TREE REMOVAL AND RELOCATION. |
| | PLEASE NOTE CUS 1 THROUGH 3 ARE SHOWN IN LOCATIONS |
| | WHERE THE LANDSCAPE PLAN SHOWS HEDGES. |
| | B. IRRIGATION |
| | C. PARKING GARAGE ACCESS LANES, TO INCLUDE PAVING, |
| | STRIPING, AND SIGNAGE |
| | D. BICYCLE RACKS |
| | E. EXTERIOR SIGNAGE |
| | F. WORK AND IMPROVEMENTS IN THE RIGHT-OF-WAY |
| | G. FENCES AND GATES NOT LOCATED WITHIN THE GARAGE |
| | H. GENERATOR AND ENCLOSURE |
| | I. HARDSCAPE, TO INCLUDE THE PAVERED ENTRY AREA AND |
| | SIDEWALKS |
| | J. SITE LIGHTING, TO INCLUDE PEDESTRIAN BOLLARDS - |
| | NOTE: THE PHILIPS LUMEC LEONIS SERIES OF LIGHTING DOES |
| | NOT COMPLY WITH THE DOWNTOWN STREET LIGHTING |
| | REQUIREMENTS ? THE FIXTURE SHALL BE MOUNTED ON TOP OF |
| | THE POLE WITH THE LAMP CENTER AT 17 FEET ABOVE GRADE. |
| | THE PHILIPS LUMEC URBANSCAPE PRODUCT MOUNTED ON A POLE |
| | APPEARS THAT IT WOULD COMPLY WITH THE DOWNTOWN |
| | REQUIREMENTS. PLEASE REMEMBER THAT PALM BEACH COUNTY |
| | COMMITTED TO COORDINATING WITH RELATED TO USE THE SAME |
| | OR SIMILAR LIGHT FIXTURES IN THE FLORIDA AVENUE |
| | RIGHT-OF-WAY AND THE ENTRY DRIVE AND PLAZA TO MAINTAIN |
| | CONSISTENCY BETWEEN THE TWO PROJECTS. |
| | K. WORK WITHIN THE FUTURE STAGING AREA |
| | |
| | 2) SHEET AE160 HAS AN ARROW CALLING OUT THE ADA ACCESS |
| | AISLE AS YELLOW STRIPING. THIS STRIPING SHALL BE BLUE, |
| | NOT YELLOW. |
| | |
| | 3) SHEET AE501 AND SHEETS SW 120-SW170 DO NOT SHOW |
| | COMPLIANCE WITH THE CONDITION THAT THE SIGNS WITHIN THE |
| | CONVENTION CENTER GARAGE GUIDE USERS TO THE ELEVATORS |
| | AND STAIRWELLS AT THE NORTHWEST CORNER OF THE |
| | CONVENTION CENTER GARAGE AND CLEARLY SIGN THE REMAINING |
| | STAIRWELLS AS EMERGENCY EGRESS ONLY. SIGN S23 BEING |
| | SHOWN AT THE NORTHEAST STAIRWELL INDICATES THAT THE |
| | STAIRWELL IS FOR NORMAL EXITING OF THE GARAGE. IF THIS |
| | IS THE CASE, THEN THE EXIT TO THE STAIRWELL NEEDS TO BE |
| | CONNECTED INTO THE SITE SIDEWALK NETWORK ALONG THE |
| | NORTH SIDE OF THE GARAGE WITH NO LOSS OF LANDSCAPE. |
| | SIGN TYPE S22 IS SHOWN ON THE PLAN BUT NO DETAIL OF |
| | THIS SIGN IS INCLUDED. |
| | |
| | 4) THE PHOTOMETRICS ON EACH FLOOR NEED TO BE CONTINUED |
| | OUTSIDE OF THE GARAGE WALL TO THE PROPERTY LINE AROUND |
| | THE GARAGE. |
| | |
| | 5) PROVIDE INFORMATION ON HOW GLARE FROM THE INTERIOR |
| | AND EXTERIOR LIGHTS ONTO THE ADJACENT RESIDENTIAL |
| | PROPERTY AND RIGHTS-OF-WAY WILL BE CONTROLLED. |
| | |