| Date |
Text |
| 2015-06-24 14:57:21 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | |
| | 1) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE |
| | BASEMENT LEVEL PARKING GARAGE TO VERIFY EF-1, 2, & 3 |
| | HAVE BEEN SIZED TO PROVIDE THE RATES REQUIRED BY TABLE |
| | 403.3 AND SECTION 404 FBC-10 MECHANICAL. |
| | 2) CLARIFY THE METHOD BY WHICH THE STAIR PRESSURIZATION |
| | FANS (EF-4, 5 AND SF-1,2) WERE SIZED: PROVIDE |
| | CALCULATIONS CONSISTENT WITH SECTION 909.6 INCLUSIVE |
| | FBC-10 BUILDING. |
| | 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| | BOOSTER PUMP, STORAGE, AND FIRE PUMP ROOMS- ASHRAE |
| | 62.1-07. |
| | 4) PROVIDE AC LOAD CALCULATIONS FOR ALL CONDITIONED |
| | ROOMS AND SPACES IN ACCORDANCE WITH ACCA MANUAL N, OR |
| | ASHRAE/ACCA STANDARD 183- REFERENCE SECTION 503.2.1 |
| | FBC-10 ENERGY CONSERVATION. |
| | 5) PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED PROJECT |
| | PER SECTION101 FBC-10 ENERGY: SUBMIT TWO COPIES OF |
| | EITHER FORM 502 OR 506 SIGNED BY THE DESIGN |
| | PROFESSIONAL OF RECORD. |
| | 6) SHEET MM110: PROVIDE ADDITIONAL DETAILS OR NOTES |
| | INDICATING THE SPACING AND MOUNTING HEIGHT LOCATIONS OF |
| | THE C0 DETECTORS PER THE MANUFACTURER'S |
| | RECOMMENDATIONS. LIST THE MAKE AND MODEL NUMBERS OF THE |
| | DEVICES AND SUBMIT PRODUCT DATA SHEETS REVIEWED AND |
| | APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. |
| | 7) MM220: CU 3 & 6 SHOWN IN DETAIL 8 SHALL BE INSTALLED |
| | A MINIMUM OF 8 FT. ABOVE THE FLOOR PER SECTION 304.6 |
| | FBC-10 MECH. |
| | 8) MM230: THE BOTTOM OF THE EXHAUST LOUVERS FOR THE |
| | BASEMENT EXHAUST FANS AS SHOWN IN DETAIL 4 SHALL BE |
| | INSTALLED A MINIMUM OF 10 FT. ABOVE THE ADJOINING |
| | GRADE- SECTION 501.2.1(2) FBC-10 MECH. |
| | 9) MM801: THE RECIRCULATING FANS SHOWN IN DETAIL 11 |
| | SHALL BE INSTALLED AT LEAST 1FT. HIGHER THAN THE GARAGE |
| | DOOR PER SECTION 304.6. |
| | 10) MM801: PROVIDE INSTALLATION DETAILS FOR THE |
| | FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS. |
| | 11) PROVIDE A SUBMITTAL PACKAGE PREPARED BY THE DESIGN |
| | PROFESSIONAL OF RECORD THAT INCLUDES: A) FLORIDA |
| | PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE ROOF |
| | MOUNTED EXHAUST FANS, THE INTAKE AND EXHAUST LOUVERS, |
| | AND THE CONDENSER WALL MOUNT BRACKETS. B) |
| | MANUFACTURER'S SPECIFICATIONS FOR THE EXHAUST AND |
| | INTAKE FANS, THE AC UNITS, THE MOTORIZED INTAKE |
| | DAMPERS, THE C0 DETECTORS, THE RECIRCULATION FANS, THE |
| | FIRE/SMOKE DAMPERS, AND THE DUCT SMOKE DETECTORS. IN |
| | REGARD TO ALL EXTERIOR INSTALLATIONS SUBJECT TO WIND |
| | LOAD, THE DESIGN PROFESSIONAL OF RECORD SHALL CALCULATE |
| | DESIGN PRESSURES AND PROVIDE TIE-DOWN ENGINEERING, AND |
| | ALSO CIRCLE OR HIGHLIGHT ALL APPLICABLE NOTES AND |
| | DETAILS IN THE NOA'S AND PRODUCT APPROVALS. |
| | 12) PLEASE NOTE THAT THE ABOVE REVIEW COMMENTS ARE |
| | BASED ON THE BUILDING BEING CLASSIFIED AS AN "OPEN |
| | PARKING GARAGE" BY THE DESIGN PROFESSIONAL OF RECORD. |
| | THIS CLASSIFICATION IS BEING CHALLENGED BY THE WEST |
| | PALM BEACH FIRE AND RESCUE DEPT., THEREFORE ADDITIONAL |
| | COMMENTS MAY FOLLOW THIS REVIEW. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |