| Plan Review Notes For Permit 15060123 |
| Permit Number |
15060123 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-16 19:36:19 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. NEC 408.4 REQUIRES THAT YOU PROVIDE AN ACCURATE | | | PANEL SCHEDULE IDENTIFYING ALL CIRCUITS. | | | 2. NEC 230.72(C) REQUIRES THAT ALL OCCUPANT HAVE ACCESS | | | TO THE DISCONNECTING MEANS FOR THEIR UNITS, INDICATE ON | | | THE PLANS THE LOCATION OF SUCH. | | | 3. NEC 220.16 PROVIDE THE REQUIRED ELECTRICAL LOAD | | | CALCS IN ACCORDANCE WITH 220.12 EDUCATIONAL OCCUPANCY 3 | | | W/SQ FT. | | | 4. NEC 210.8(7) REQUIRES ALL OUTLETS WITH 6' OF A SINK | | | TO BE GFI PROTECTED. | | | 5. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET ABOVE | | | EVERY ENTRANCE DOOR. | | | 6. FBC-E SECTION 505 HAS SPECIFIC AND MANDATORY | | | LIGHTING REQUIREMENTS WHICH SHALL BE ADDRESSED. | | | 7. FBC-B 1006.2 HAS SPECIFIC EMERGENCY LIGHTING | | | REQUIREMENTS WHICH DO NOT APPEAR TO HAVE BEEN MET. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | |
|