| Plan Review Notes For Permit 15060115 |
| Permit Number |
15060115 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-05 17:17:19 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE 2010 FBC | | | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R14 | | | SUBMITTED: | | | A) THE DESIGN PRESSURES FOR THE SELECTED ASSEMBLY | | | (W-49) IS -90PSF. THIS BUILDING IS LOCATED IN EXPOSURE | | | "C". THE CORNER PRESSURES FOR THIS BUILDING ARE HIGHER | | | THAN -90PSF. THIS ASSEMBLY CAN NOT BE USED BECAUSE | | | RATIONAL ANALYSIS IS NOT ALLOWED FOR NAIL ENHANCING. | | | SEE NOTE #9 ON PAGE 2 OF 33. NEED TO SELECT ANOTHER | | | ASSEMBLY THAT MEETS ALL THE DESIGN PRESSURES OR ANOTHER | | | ASSEMBLY THAT ALLOWS RATIONAL ANALYSIS (SIGNED AND | | | SEALED RAS 117 CALCULATIONS). OR PROVIDE ANOTHER | | | PRODUCT APPROVAL. SEC. 1609 OF 2010 FBC-BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|