| 2015-07-23 12:10:37 | 7/23/2015 |
| | PROJECT: MARY FISHER RENOVATION |
| | PERMIT#: 15060110 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A LUMINAIRE SCHEDULE INDICATING COMPLIANCE |
| | WITH THE FBC-E, THE NEC 110.3, AND 410. |
| | |
| | 2) PROVIDE A PANEL SCHEDULE THAT INCLUDES THE OCPD AND |
| | CORRESPONDING WIRE SIZES AND WIRING METHODS PROPOSED. |
| | NEC 408.4. |
| | THE PANEL SCHEDULE INCLUDED IN THE RESUBMITTAL PROVIDES |
| | NAMES OF CIRCUITS ONLY. BREAKER AND WIRE SIZES ARE |
| | REQUIRED. THERE IS NO WAY TO VERIFY COMPLIANCE WITHOUT |
| | THIS INFORMATION. |
| | |
| | 3) INDICATE COMPLIANCE WITH THE FBC FOR ANY |
| | PENETRATIONS OF WALLS OR FLOOR/CEILING ASSEMBLIES |
| | REQUIRED TO BE FIRE-RESISTANCE RATED. THESE |
| | PENNETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH THE |
| | FBC-R302. |
| | |
| | 4) ALL NEW 120-VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH |
| | CIRCUITS SUPPLYING OUTLETS INSTALLED IN THE DWELLING |
| | UNIT SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT |
| | INTERRUPTER FOR THE PROTECTION OF THE BRANCH CIRCUIT. |
| | NEC 210.12 |
| | |
| | 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT. NEC 406.11 |
| | |
| | 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM, |
| | SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, |
| | COMMUNICATION AS NEEDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |