Plan Review Notes
Plan Review Notes For Permit 15060110
Permit Number 15060110
Review Stop E
Sequence Number 2
Notes
Date Text
2015-07-23 12:10:377/23/2015
 PROJECT: MARY FISHER RENOVATION
 PERMIT#: 15060110
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A LUMINAIRE SCHEDULE INDICATING COMPLIANCE
 WITH THE FBC-E, THE NEC 110.3, AND 410.
  
 2) PROVIDE A PANEL SCHEDULE THAT INCLUDES THE OCPD AND
 CORRESPONDING WIRE SIZES AND WIRING METHODS PROPOSED.
 NEC 408.4.
 THE PANEL SCHEDULE INCLUDED IN THE RESUBMITTAL PROVIDES
 NAMES OF CIRCUITS ONLY. BREAKER AND WIRE SIZES ARE
 REQUIRED. THERE IS NO WAY TO VERIFY COMPLIANCE WITHOUT
 THIS INFORMATION.
  
 3) INDICATE COMPLIANCE WITH THE FBC FOR ANY
 PENETRATIONS OF WALLS OR FLOOR/CEILING ASSEMBLIES
 REQUIRED TO BE FIRE-RESISTANCE RATED. THESE
 PENNETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH THE
 FBC-R302.
  
 4) ALL NEW 120-VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN THE DWELLING
 UNIT SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
 INTERRUPTER FOR THE PROTECTION OF THE BRANCH CIRCUIT.
 NEC 210.12
  
 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT. NEC 406.11
  
 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION AS NEEDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  