| 2015-07-07 16:35:37 | 7/7/2015 |
| | PROJECT: MARY FISHER RENOVATION |
| | PERMIT#: 15060110 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) RECESSED LUMINAIRES INSTALLED IN THE BUILDING |
| | THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | UNCONDITIONED SPACES. FBC-E 502.3.8 RECESSED LIGHTING. |
| | |
| | 2) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL. |
| | |
| | 3) PROVIDE A PANEL SCHEDULE. NEC 408.4 |
| | |
| | 4) PROVIDE A SCOPE OF WORK DELINIATING BETWEEN WHAT IS |
| | EXISTING TO REMAIN AND WHAT IS PROPOSED TO BE INSTALLED |
| | NEW. |
| | |
| | 5) PROVIDE A GFI OUTLET ON THE BALCONIES. NEC |
| | 210.52(E)(3). |
| | |
| | 6) PROVIDE RECEPTACLES SO THAT NO POINT MEASURED |
| | HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL SPACE IS |
| | MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE OUTLET. 210.52 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |