| 2015-06-25 06:27:57 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060073 |
| | ADD: 529 S. FLAGLER DR. SUITE # 15E |
| | CONT: CAMBRIDGE CONSTRUCTION |
| | TEL: ( 561)784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JUNE 25/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS CREATED BY KEITH CARRINGTON DESIGNS DOES |
| | NOT COMPLY WITH FLORIDA ADMINISTRATIVE CODE; 61 G |
| | 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000 |
| | THE PERSONAL SEAL, SIGNATURE AND DATE OF THE INTERIOR |
| | DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR INTERIOR |
| | DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD AND |
| | SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS |
| | CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT. |
| | DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE |
| | RESPONSIBLE INTERIOR DESIGNER. FINAL OFFICIAL RECORD |
| | DOCUMENTS (NOT TRACINGS, ETC.) SHALL BE SO SIGNED. THE |
| | SIGNING AND SEALING OF THE SPECIFICATION INDEX SHEETS |
| | SHALL BE CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND |
| | PAGES SHALL BE SO SIGNED AND SEALED. AN INTERIOR |
| | DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS |
| | SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR |
| | OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR |
| | UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED |
| | IN RULE CHAPTER 61G1-23, F.A.C. AN INTERIOR DESIGNER |
| | SHALL NOT USE HIS SEAL OR DO ANY OTHER ACT AS AN |
| | INTERIOR DESIGNER UNLESS HOLDING AT THE TIME A |
| | CERTIFICATE OF REGISTRATION AND ALL REQUIRED RENEWALS |
| | THEREOF. |
| | |
| | FL. S. 481.023 DEFINITIONS (8) ?INTERIOR DESIGN? MEANS |
| | DESIGNS, CONSULTATIONS, STUDIES, DRAWINGS, |
| | SPECIFICATIONS, AND ADMINISTRATION OF DESIGN |
| | CONSTRUCTION CONTRACTS RELATING TO NONSTRUCTURAL |
| | INTERIOR ELEMENTS OF A BUILDING OR STRUCTURE. ?INTERIOR |
| | DESIGN? INCLUDES, BUT IS NOT LIMITED TO, REFLECTED |
| | CEILING PLANS, SPACE PLANNING, FURNISHINGS, AND THE |
| | FABRICATION OF NONSTRUCTURAL ELEMENTS WITHIN AND |
| | SURROUNDING INTERIOR SPACES OF BUILDINGS. ?INTERIOR |
| | DESIGN? SPECIFICALLY EXCLUDES THE DESIGN OF OR THE |
| | RESPONSIBILITY FOR ARCHITECTURAL AND ENGINEERING WORK, |
| | EXCEPT FOR SPECIFICATION OF FIXTURES AND THEIR LOCATION |
| | WITHIN INTERIOR SPACES. AS USED IN THIS SUBSECTION, |
| | ?ARCHITECTURAL AND ENGINEERING INTERIOR CONSTRUCTION |
| | RELATING TO THE BUILDING SYSTEMS? INCLUDES, BUT IS NOT |
| | LIMITED TO, CONSTRUCTION OF STRUCTURAL, MECHANICAL, |
| | PLUMBING, HEATING, AIR-CONDITIONING, VENTILATING, |
| | ELECTRICAL, OR VERTICAL TRANSPORTATION SYSTEMS, OR |
| | CONSTRUCTION WHICH MATERIALLY AFFECTS LIFESAFETY |
| | SYSTEMS PERTAINING TO FIRESAFETY PROTECTION SUCH AS |
| | FIRE-RATED SEPARATIONS BETWEEN INTERIOR SPACES, |
| | FIRE-RATED VERTICAL SHAFTS IN MULTISTORY STRUCTURES, |
| | FIRE-RATED PROTECTION OF STRUCTURAL ELEMENTS, SMOKE |
| | EVACUATION AND COMPARTMENTALIZATION, EMERGENCY INGRESS |
| | OR EGRESS SYSTEMS, AND EMERGENCY ALARM SYSTEMS. |
| | |
| | FL. S. 481.213?LICENSURE.(2)?THE BOARD SHALL CERTIFY |
| | FOR LICENSURE BY EXAMINATION ANY APPLICANT WHO PASSES |
| | THE PRESCRIBED LICENSURE EXAMINATION AND SATISFIES THE |
| | REQUIREMENTS OF SS. 481.209, FOR INTERIOR DESIGNERS. |
| | |
| | 2) APPROVED, WHISPER MAT CS DOES MEET ALL OF THE |
| | REQUIRED ASTM STANDARDS, ASTM E-90, ASTM E-492 & ASTM |
| | E-84. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |