| Plan Review Notes For Permit 15060073 |
| Permit Number |
15060073 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-03 12:32:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THERE IS INSUFFICIENT DETAIL TO APPROVE THE PROPOSED | | | PROJECT. | | | | | | PROVIDE EXISTING AND PROPOSED DETAILS. | | | | | | THE NATURE OF THE REMODEL MAY REQUIRE AN EVALUATION OF | | | THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE | | | AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF | | | WALLS/CEILINGS REQUIRES AN EVALUATION AND/OR PROTECTION | | | OF THE LIFE SAFETY DEVICES. | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | |
|