| 2015-06-17 16:23:55 | 6/17/2015 |
| | PROJECT: APARTMENT 15-E |
| | PERMIT#: 15060073 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | SEE BUILDING REVIEW NOTES. COMPLY WITH BUILDING REVIEW |
| | AND INCLUDE ALL ELECTRICAL ELEMENTS ON NEW PLANS WHEN |
| | RESUBMITING. IN ADDITION INCLUDE THE FOLLOWING |
| | ELECTRICAL ELEMENTS IN THE NEW PLANS PER THE 2010 |
| | FLORIDA BUILDING CODE AND THE 2008 NATIONAL ELECTRICAL |
| | CODE. |
| | |
| | 1) FBC-RESIDENTIAL 314 AND 315. ADD SMOKE DETECTORS AS |
| | REQUIRED FOR NEW CONSTRCTION.: WHEN ALTERATIONS, |
| | REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| | ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| | EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| | BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| | NEW DWELLINGS. |
| | |
| | 2) NEC 210.12, 406.11ALL NEW GENERAL PURPOSE OUTLETS |
| | MUST BE TAMPER RESISTANT AND AFCI PROTECTED. |
| | |
| | 3) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. |
| | 3A) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. |
| | 3(B) NEC 210.8.(A) ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| | SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1) |
| | BATHROOMS. |
| | |
| | 4) NEC 210.52(C)(1) WALL COUNTERTOP SPACES. A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. |
| | |
| | 5) FBC-E 502.3.8 RECESSED LIGHTING. RECESSED LUMINAIRES |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | AND AIR TIGHT RATED AND SEALED TO LIMIT AIR LEAKAGE |
| | BETWEEN CONDITIONED AND UNCONDITIONED SPACES. |
| | |
| | 6) NEC 408.4 PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT |
| | AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS |
| | TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. |
| | |
| | 7) NEC 220.16 LOADS FOR NEW CIRCUITS OR EXTENDED |
| | CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE |
| | CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14, |
| | AS APPLICABLE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |