Plan Review Notes
Plan Review Notes For Permit 15060045
Permit Number 15060045
Review Stop R
Sequence Number 2
Notes
Date Text
2015-09-02 16:02:40ROOFING PLAN REVIEW
 W. P. B. PERMIT: 15060045
 ADD: 2224 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETEMINED
 TEL: ( 305)710-1118
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 02/2015
 ACTION: DENIED
  
 1A) A ROOFING PERMIT WILL BE REQUIRED FOR THE NEW
 STANDING SEAM METAL ROOFING AND FLAT ROOF REPAIRS. THE
 SUBMITTED PRODUCT APPROVALS WERE NOT REVIEWED BY THE
 DESIGNER OF RECORD. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 FLAT ROOF NOA SUBMITTED 12-0307.02 FIRESTONE ULTRAPLY
 TPO SINGLE PLY ROOF SYSTEMS OVER WOOD DECK. NOTE NO
 SUB-SYSTEM WAS IDENTIFIED, VARIOUS SUB-SYSTEMS HAVE
 VARYING PRESSURES. WILL NEED RAS 117 CALCULATIONS BY A
 SIGNED & SEALED BY A DESIGN PROFESSIONAL.
  
 STEEL ROOF PANELS NOA 10-1018.04 ONCE REVIEWED BY
 DESIGN PROFESSIONAL AND SHOP DRAWING STAMP OF APPROVAL
 IS AFFIXED WE WILL BE ABLE TO REVIEW FOR CODE
 COMPLIANCE.
  
 (G) PRE-ENGINEERED CURBS, EXHAUST FANS & CURB NOR A/C
 STANDS
 NOTE, THE ROOF TOP CURB FOR THE RTU UNITS PRODUCT
 APPROVAL CAN NOT BE VERIFIED, IT IS A OLDER REVSION AND
 NOT WHAT IS ON THE FLORIDA WEBSITE UNDER FL 1503.1.
 PLEASE UPDATE AND ALSO INCLUDE THE FLORIDA PRODUCT
 APPROVAL COVERSHEET IDENTIFING WHICH REVISION IT IS.
  
 NO PRE-ENGINEERED A/C STANDS OR EXHAUST FANS SUBMITTED
 SHOWN ON SHEET A1.08 & M0.1.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  