Plan Review Notes
Plan Review Notes For Permit 15060045
Permit Number 15060045
Review Stop P
Sequence Number 2
Notes
Date Text
2015-08-28 14:03:411) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND LABELED
 PER THE 2010 FBC-FUEL GAS SEC.301.3. 2ND REQUEST.
 2) SUBMIT TWO COPIES OF MANUF. INSTALLATION
 INSTRUCTIONS FOR THE CONCENTRIC VENT FOR GWH-2. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT FACTORY SIZING CALCULATIONS DONE BY SCHIER
 FOR THE GREASE TRAPS PER THE 2010 FBC-PLUMBING
 SEC.1003.2.CONTACT LEE SCHNEEWEISS AT 1-800-538-4792.
 2ND REQUEST.
 4) THE BRANCH VENT CONNECTING THE VENTS FROM THE MEN'S
 AND WOMEN'S RESTROOM EXCEEDS 40 FT. IN DEVELOPED LENGTH
 AND SHALL BE INCREASED ONE PIPE SIZE FOR IT'S ENTIRE
 LENGTH PER FBC-PLUMBING SEC.916.4.1.
 (NOTE: THE PREVIOUS COMMENT HAD A TYPO ERROR. IT READ
 "OR IT'S ENTIRE LENGTH" WHEN IT SHOULD HAVE READ "FOR
 IT'S ENTIRE LENGTH." )
 5) SHT.P0.1 - THE TOTAL FLOW- THRU FOR THE INTERCEPTORS
 IS SHOWN AS 85 GPM BUT THE TOTAL GPM IS SHOWN AS
 95.08.PLEASE CLARIFY THE DIFFERENCE WITH THESE TWO
 NUMBERS. I WOULD THINK THEY SHOULD BE THE SAME.
 6) SHT. P3.1 - MY TABULATION OF THE SECTIONS OF GAS
 PIPE FOR THE DEVELOPED LENGTH IS 143 FT. THE GAS
 INFORMATION BOX NOTES 125 FT.THE PIPING IS SIZED
 CORRECTLY IN ITS ENTIRETY.PLEASE CHECK YOUR TABULATION
 AND MAKE ANY NECESSARY CORRECTION TO THE INFFORMATION.
 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR BOTH OF THE
 WATER HEATERS AND KITCHEN EQUIPMENT PER THE 2010 FBC-
 FUEL GAS CODE SEC.304. NOTE #18 ON SHT.M1.1 REFERS TO
 SEC.306.6.2 OF 2010 FGC. THERE IS NO SUCH CODE SECTION.
 REFER TO 2010 FGC SEC.304.6.2 FOR COMBUSTION AIR FOR
 THE WATER HEATERS. PER SEC.304.10, THE NET FREE AREA OF
 METAL LOUVERS IS ASSUMED TO BE 75%,
 8) PER 2010 FBC TABLE 403.1 FOOTNOTE G, A UNISEX TOILET
 ROOM SHALL BE PROVIDED. THE ROUTE TO PUBLIC TOILET
 FACILITIES SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS PER 2010 FBC-PLUMBING SEC.403.3.1.
  
 PLUMBING PLAN REVIEW