| 2015-09-03 13:39:22 | 2ND REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060045 |
| | 9/3/15 |
| | |
| | 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS- PLEASE |
| | COMPLY. 3) THE DESIGN PROFESSIONALS OF RECORD SHALL |
| | SIGN AND SEAL ALL THE MECHANICAL AND KITCHEN HOOD PLAN |
| | SHEETS IN COMPLIANCE WITH SECTION 61G15-23.002 FL. |
| | ADMIN. CODE. |
| | 2) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS- PLEASE |
| | COMPLY. 4) SHEET M0.1, DETAILS M3, M4, M7, M8, & M11: |
| | WINDLOAD TIE-DOWN ENGINEERING DETAILS ARE REQUIRED FOR |
| | THE ROOF TOP HVAC INSTALLATIONS SHOWN IN THE DETAILS, |
| | ALONG WITH FL. PRODUCT AND/OR MIAMI-DADE NOA'S REVIEWED |
| | AND STAMPED BY THE DESIGN PROFESSIONAL OF RECORD. |
| | SUBMIT ALL THE REQUIRED DOCUMENTS, AND REVISE THE |
| | DETAILS TO INCLUDE CURB HEIGHTS, AND STAND CLEARANCE |
| | HEIGHTS ABOVE THE ROOF. THE ENGINEER OF RECORD SHALL |
| | PROVIDE THE WIND DESIGN CRITERIA ON THE PLANS AND |
| | COMPLETE DETAILS FOR ALL ROOF-MOUNTED EQUIPMENT |
| | INCLUDING MODIFICATIONS TO THE EXISTING ROOF STRUCTURE, |
| | AND THE TYPES, SIZES, AND SPACINGS OF ANCHORS AND |
| | FASTENERS FOR ATTACHING THE ROOF CURBS TO THE |
| | STRUCTURE, AND MOUNTING THE EQUIPMENT TO THE CURBS AND |
| | STANDS. PLEASE REFER TO DETAIL M3 ON SHEET M0.1 AND |
| | INDICATE THE EXACT PLAN SHEETS WHERE THE DETAILS CAN BE |
| | FOUND. |
| | 3) COMMENT #5 FROM THE 1ST REVIEW STILL EXISTS- PLEASE |
| | COMPLY. 5) M0.1, DETAIL 6: UPDATE THE SMACNA HANGER |
| | TABLE TO 5-1 & FIG. 5-5 PER THE 2005 EDITION IN EFFECT. |
| | 4) COMMENT #6 FROM THE 1ST REVIEW HAS BEEN ADDRESSED ON |
| | THE PLANS, HOWEVER THERE APPEARS TO BE INADEQUATE O/A |
| | FOR THE MAN CAVE AREA BASED ON TABLE 403.3. THE AREA IS |
| | APPROXIMATELY 650 SQ. FT. WHICH AMOUNTS TO |
| | APPROXIMATELY 454 CFM'S OF O/A BY THE TABLE, OR 274 BY |
| | THE AMOUNT OF SEATS (21). |
| | 5) COMMENT #9 FROM THE 1ST REVIEW STILL EXISTS- PLEASE |
| | COMPLY. IN RESPONSE TO THIS COMMENT REGARDING DUCT |
| | SMOKE DETECTOR SEQUENCE OF OPERATIONS, THE DESIGN |
| | PROFESSIONAL HAS STATED IN THE NARRATRIVE RESPONSE THAT |
| | THE COMPLIANCE INFORMATION WOULD BE FOUND ON SHEET |
| | FA0.1 WHCICH WAS NOT INCLUDED WITH THE CORRECTED PLAN |
| | SETS. PLEASE PROVIDE THE SHEET. |
| | 6) COMMENT #10 FROM THE 1ST REVIEW HAS BEEN ADDRESSED |
| | HOWEVER NO CONDENSATE DISPOSAL DETAILS ARE SHOWN FOR |
| | RTU #3. IN ADDITION PLEASE INDICATE HOW THE NEW |
| | CONDENSATE PIPES WILL BE SUPPORTED AND PROTECTED FROM |
| | UV DEGRADATION. |
| | 7) COMMENT #12 FROM THE 1ST REVIEW HAS BEEN ADDRESSED |
| | HOWEVER THE ENERGY CALCULATION FORM 506-2010 DOES NOT |
| | INCLUDE ANY DATA FOR THE OAU AAON RTU- PLEASE REVISE |
| | ACCORDINGLY. |
| | 8) REFER TO BUILDING COMMENTS FOR ADDITIONAL ROOF TOP |
| | EQUIPMENT REQUIREMENTS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |