2015-09-03 13:39:222ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060045
 9/3/15
  
 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. 3) THE DESIGN PROFESSIONALS OF RECORD SHALL
 SIGN AND SEAL ALL THE MECHANICAL AND KITCHEN HOOD PLAN
 SHEETS IN COMPLIANCE WITH SECTION 61G15-23.002 FL.
 ADMIN. CODE.
 2) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. 4) SHEET M0.1, DETAILS M3, M4, M7, M8, & M11:
 WINDLOAD TIE-DOWN ENGINEERING DETAILS ARE REQUIRED FOR
 THE ROOF TOP HVAC INSTALLATIONS SHOWN IN THE DETAILS,
 ALONG WITH FL. PRODUCT AND/OR MIAMI-DADE NOA'S REVIEWED
 AND STAMPED BY THE DESIGN PROFESSIONAL OF RECORD.
 SUBMIT ALL THE REQUIRED DOCUMENTS, AND REVISE THE
 DETAILS TO INCLUDE CURB HEIGHTS, AND STAND CLEARANCE
 HEIGHTS ABOVE THE ROOF. THE ENGINEER OF RECORD SHALL
 PROVIDE THE WIND DESIGN CRITERIA ON THE PLANS AND
 COMPLETE DETAILS FOR ALL ROOF-MOUNTED EQUIPMENT
 INCLUDING MODIFICATIONS TO THE EXISTING ROOF STRUCTURE,
 AND THE TYPES, SIZES, AND SPACINGS OF ANCHORS AND
 FASTENERS FOR ATTACHING THE ROOF CURBS TO THE
 STRUCTURE, AND MOUNTING THE EQUIPMENT TO THE CURBS AND
 STANDS. PLEASE REFER TO DETAIL M3 ON SHEET M0.1 AND
 INDICATE THE EXACT PLAN SHEETS WHERE THE DETAILS CAN BE
 FOUND.
 3) COMMENT #5 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. 5) M0.1, DETAIL 6: UPDATE THE SMACNA HANGER
 TABLE TO 5-1 & FIG. 5-5 PER THE 2005 EDITION IN EFFECT.
 4) COMMENT #6 FROM THE 1ST REVIEW HAS BEEN ADDRESSED ON
 THE PLANS, HOWEVER THERE APPEARS TO BE INADEQUATE O/A
 FOR THE MAN CAVE AREA BASED ON TABLE 403.3. THE AREA IS
 APPROXIMATELY 650 SQ. FT. WHICH AMOUNTS TO
 APPROXIMATELY 454 CFM'S OF O/A BY THE TABLE, OR 274 BY
 THE AMOUNT OF SEATS (21).
 5) COMMENT #9 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY. IN RESPONSE TO THIS COMMENT REGARDING DUCT
 SMOKE DETECTOR SEQUENCE OF OPERATIONS, THE DESIGN
 PROFESSIONAL HAS STATED IN THE NARRATRIVE RESPONSE THAT
 THE COMPLIANCE INFORMATION WOULD BE FOUND ON SHEET
 FA0.1 WHCICH WAS NOT INCLUDED WITH THE CORRECTED PLAN
 SETS. PLEASE PROVIDE THE SHEET.
 6) COMMENT #10 FROM THE 1ST REVIEW HAS BEEN ADDRESSED
 HOWEVER NO CONDENSATE DISPOSAL DETAILS ARE SHOWN FOR
 RTU #3. IN ADDITION PLEASE INDICATE HOW THE NEW
 CONDENSATE PIPES WILL BE SUPPORTED AND PROTECTED FROM
 UV DEGRADATION.
 7) COMMENT #12 FROM THE 1ST REVIEW HAS BEEN ADDRESSED
 HOWEVER THE ENERGY CALCULATION FORM 506-2010 DOES NOT
 INCLUDE ANY DATA FOR THE OAU AAON RTU- PLEASE REVISE
 ACCORDINGLY.
 8) REFER TO BUILDING COMMENTS FOR ADDITIONAL ROOF TOP
 EQUIPMENT REQUIREMENTS.
  