| 2015-09-14 14:09:02 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. ONE OF THE TWO SETS OF PLANS IS MISSING SHEET E0.1 | | | 2. COMMENTS 4, 5 & 6 WERE DELEGATED TO THE ARCHITECT | | | WHO HAS NOT YET COMPLETED HIS CORRECTIONS/RESPONSES TO | | | THESE NOTES. | | | 3. YOUR RESPONSE TO NOTE 8 STATES THAT THE SHOW WINDOW | | | OUTLETS ARE INCLUDED ON THE DRAWINGS AND HAVE BEEN | | | INCLUDED ON THE CALCULATIONS. THE OUTLETS INDICATED | | | ABOVE THE WINDOWS, ACCORDING TO PANEL ?A? SCHEDULE ARE | | | FOR THE MOTORIZED SHADES. | | | 4. YOU INDICATE THAT THERE ARE FOUR (4) LOCATIONS | | | INDICATED FOR SIGN OUTLETS. THAT IS ALL FINE, YOU MAY | | | ALL THE SIGNAGE YOU DECIDE AS LONG AS YOU HAVE AT LEAST | | | THOSE REQUIRED BY CODE BY EVERY DOOR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|