| 2015-09-03 08:54:05 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060045 |
| | ADD: 2224 PALM BEACH LAKES BLVD. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ( 305)710-1118 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. SEPT. 02/2015 |
| | ACTION: DENIED |
| | |
| | 1) THIS BUILDING WILL NEED TO HAVE A RESIDENT INSPECTOR |
| | ON SITE. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: (2) . |
| | FOR ALL MAJOR STRUCTURAL ALTERATIONS. |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| | SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| | COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| | WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| | ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| | SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| | CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| | IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| | ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | 1A) FORMS SUBMITTED ARE COPIES NOT ORIGINAL NOTARIZED |
| | DOCUMENTS. RESIDENT INSPECTOR FORMS WERE |
| | E-MAILED TO ;[email protected] |
| | RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES |
| | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. |
| | |
| | 1B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 1C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 1D) NOTE ONLY (2) SETS OF PLANS WERE RETURNED. NOTE FOR |
| | PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. FOR |
| | DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT |
| | LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. |
| | |
| | 1E) PLEASE CALL THE CITY OF WEST PALM BEACHES? |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 2-4) COMPLIED |
| | |
| | 5) LS1.01 HAS A NOTE THAT FIRE ALARM DRAWINGS SHALL BE |
| | REQUIRED PRIOR TO THE GC STARTS WORK. SECTION 907.2.1 |
| | DOES REQUIRE A FIRE ALARM FOR AN A2 ASSEMBLY OCCUPANCY |
| | WHEN THERE IS A OCCUPANT LOAD OF 300 OR MORE. NOTE A |
| | SEPARATE PERMIT IS REQUIRED WITH DRAWINGS. |
| | |
| | 6) THE COVERSHEET NOTES THAT NEW EXTERIOR GLAZING |
| | SYSTEMS, STOREFRONT WINDOWS AND DOORS WILL BE PART OF |
| | THIS PROJECT. PLEASE SHOW COMPLIANCE WITH: COMPONENTS & |
| | CLADDING |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | NOTE: MANY OF THE PRODUCT APPROVALS HAVE MORE THAN ONE |
| | TYPE OF GLAZING, IDENTIFY TYPE OF GLAZING, WIDTH, |
| | HEIGHT, TYPE OF ANCHORS AND ASSOCIATED PRESSURES. |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS SEE |
| | COMMENTS UNDER ROOF REVIEW!!! |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS, & ROOF TOP EXHAUST FANS |
| | PRE-ENGINEERED A/C STANDS HIGHLIGHT THE WIDTH, HEIGHT |
| | TO BE INSTALLED AND ASSOCIATED |
| | PRESSURES. |
| | |
| | PLEASE NOTE IF THE BUILDING WIND DESIGN CRITERIA IS |
| | CORRECT AND ASSOCIATED PRESSURES THE PRODUCT APPROVALS |
| | CAN BE A DEFERRED SUBMITTAL IS THE DESIGN PROFESSIONAL |
| | AND OR CONTRACTOR INDICATES SUCH IN A WRITTEN RESPONSE. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 7) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS,? |
| | |
| | 8) 2ND REQUEST. COPIES SUBMITTED, 3 ORIGINAL SIGNED AND |
| | SEALED DOCUMENTS. THE STRUCTURAL SHEET S-1 GRIDLINE ?L? |
| | SHOWS A NEW ADDITION TO THE BUILDING BUT THERE WAS NO |
| | SOILS REPORT SUBMITTED, PLEASE SHOW COMPLIANCE WITH |
| | 2010 FBC-B 1803.5.2 QUESTIONABLE SOILS. |
| | |
| | 9) THIS SUBMITTAL THERE WAS NO DOCUMENTATION SUBMITTED |
| | AS TO HOW THE LEVEL 3 ALTERATION IS GOING TO COMPLY |
| | WITH THE 2010 FBC-ENERGY 103.2.1. |
| | |
| | 10) COMPLIED. |
| | |
| | 11)2ND REQUEST. SHEET 4 INDICATES ON VARIOUS COLUMNS |
| | THE CAPS ARE TO BE FULLY WELDED. THE TYPE OF WELD NOR |
| | THE SIZE OF THE WELD HAS BEEN IDENTIFIED. |
| | SHEET S3-5 SHOW VARIOUS COLUMNS WITH EITHER OR BOTH THE |
| | BOTTOM PLATE AND TOP PLATE BEING WELDED, THERE IS NO |
| | WELD INFORMATION ON THE PLANS AS TO TYPE OF WELD NOR |
| | THE SIZE OF THE WELD. FBC-B 2204.1. |
| | |
| | 12)2ND REQUEST. THIS DETAIL IS NOT CLEAR AS DRAWN HOW |
| | THE BAR JOIST ARE TO BE ANCHORED AS WELL AS THE 2 X6 @ |
| | 24 INCHES ON CENTER. SHEET S-4 DETAIL C IS MISSING THE |
| | ANCHORING OF THE BAR JOIST AND 2 X 6 RAFTERS TO THE |
| | W8X60 STEEL BEAM THIS IS PART OF THE MWFRS (MAIN WIND |
| | FORCE RESISTING SYSTEM). |
| | |
| | 13)2ND REQUEST. SHEET S-6 COMPONENTS AND CLADDING |
| | PRESSURES ARE LOW FOR ZONES 4 & 5. FBC-B 1609.1.5 / |
| | 1609.1.2.3.2. PLEASE NOTE THERE ARE NO PRESSURES |
| | PROVIDED FOR THE SLOPED METAL ROOFING. |
| | |
| | 14)2ND REQUEST FOR CURB DETAILS AND PRODUCT APPROVALS. |
| | SHEET # 3 FROM CAPTIVE AIR BY BUCHNANAN P. E. |
| | CONSULTING ENGINEER DOES SHOW ROOF TOP CURBS AND ROOF |
| | TOP EXHAUST FANS, NO DESIGN FOR ANCHORING OF SYSTEMS, |
| | AND NO FLORIDA PRODUCT APPROVAL SUBMITTED OR LISTED FOR |
| | THESE UNITS, THE PLANS ARE NOT SIGNED NOR SEALED BY A |
| | FLORIDA P.E. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS. |
| | |
| | 15) COMPLIED. THE PRODUCT APPROVALS SUBMITTED IS A |
| | MIAMI-DADE NOA 14-0211.09. SHEET 3 OF 7 INDICATES THE |
| | USE OF 5/16 INCH O. A. LAMINATED GLASS 1/8 INCH |
| | ANNEALED GLASS, 0.100 INCH PVB INTERLAYER AND A 3/32 |
| | INCH ANNEALED GLASS. |
| | THE 0.100 INCH PVB INTER LAYER = 2.3813 MM, REQUIRED |
| | 0.76 MM. 2010FBC-B 2405.2(1) |
| | |
| | COMMENT FROM 1ST REVIEW. SHEETS A1.01 & A2.02 DOORS |
| | IDENTIFIED AS MARK 4-7 ARE GLAZED ROLL-UP OVERHEAD |
| | DOORS. PLEASE SHOW HOW COMPLIANCE WITH FBC-B SECTION |
| | 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS. |
| | |
| | 16) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |