| 2015-06-23 09:35:11 | 1) THIS FACILITY SHALL COMPLY WITH THE EXCEPTION LISTED |
| | IN THE 2010 FBC-PLUMBING, SEC.403.1.3 - 403.1.3 POTTY |
| | PARITY. |
| | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THERE ARE |
| | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| | SECTION 553.86, FLORIDA STATUTES. |
| | EXCEPTION: THIS SECTION DOES NOT APPLY TO |
| | ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA |
| | STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING |
| | OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150 |
| | PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME |
| | NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL |
| | OF WATER CLOSETS AND URINALS FOR MEN. |
| | 2) SHT. A1.01 - SHOW THE CLEAR INSIDE DIMENSIONS OF THE |
| | EMPLOYEE RESTROOM #115. (L X W) . WPB AMEND. TO 2010 |
| | FBC SEC. 107.2.1. |
| | 3) SHT. A1.02 - PLEASE LABEL THE EMPLOYEE RESTROOM AS |
| | "UNISEX" IN LIEU OF "BOTH". THE TERM "BOTH" IS NOT CODE |
| | LANGUAGE. |
| | 4) SHT. A2.01 -ELEVATION DETAIL #8 & 15 - THE GRAB BARS |
| | SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE |
| | FROM THE FINISH FLOOR, NOT TO THE CENTERLINE AS SHOWN. |
| | 2010 FBC- ACCESSIBILITY, SEC. 609.4. |
| | 5) SHT. A2.01 - SHOW THE REQUIRED KNEE AND TOE |
| | CLEARANCES FOR THE LAVATORIES. COMPLY WITH THE FAC |
| | SEC.306. |
| | 6) SHT.P.0 - GENERAL PLUMBING NOTES #38 - AIR SHALL NOT |
| | BE USED TO TEST PLASTIC PIPE PER 2010 FPC SEC.312.1. |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND |
| | LABELED PER THE FUEL GAS CODE SEC. 301.3. |
| | 8) SUBMIT DETAILS FOR THE VENT FOR GWH-2. THE VENT |
| | SHALL COMPLY W/2010 FUEL GAS CODE SEC. 502.THE NOTE ON |
| | P0.1 REFERS TO MECHANICAL PLANS FOR LAYOUT. THERE IS NO |
| | LAYOUT ON THE MECHANICAL PLANS. CLARIFY. |
| | 9) THE GREASE TRAP CALCULATIONS SHALL BE REVIEWED BY |
| | SHIER TO ENSURE CORRECT SIZING OF THE INTERCEPTORS PER |
| | 2010 FPC SEC.1003.2.CONTACT LEE SCHNEEWEISS AT |
| | 1-800-538-4792. |
| | 10) SHT. P0.1 - MIXING VALVE DETAIL - INDICATE THE SIZE |
| | OF THE COLD WATER SUPPLY. |
| | 11) SHT. P1.2 - THE PLUMBING DRAWINGS SHALL BE SIGNED |
| | AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD PER THE |
| | FL. ADMIN. CODE. RULE 61G15-23.002. |
| | 12) INDICATE THE PSI OF THE GAS SYSTEM ON SHT.P3.1. |
| | 13) SHT.P3.2 - THE HANDICAP WATER CLOSET IN THE WOMEN'S |
| | RESTROOM SHALL BE INDIVIDUALLY VENTED OR THE SYSTEM |
| | SHALL BE DESIGNED AS A CIRCUIT VENT SYSTEM IN |
| | ACCORDANCE PER 2010 FPC SEC. 911. |
| | 14) IT APPEARS THAT THE BRANCH VENT CONNECTING THE |
| | VENTS FROM THE MEN'S & WOMEN'S RESTROOM EXCEEDS 40 FT. |
| | IN DEVELOPED LENGTH AND SHALL BE INCREASED ONE PIPE |
| | SIZE PER FPC SEC. 916.4.1 FOR IT'S ENTIRE LENGTH. |
| | 15) SUBMIT A RISER DETAIL FOR ALL THE CONDENSATE |
| | PIPING. THE MECHANICAL PLANS APPEAR TO SHOW ALL NEW |
| | RTU'S & SHT. P2.1.ONLY SHOWS RTU 5 AS BEING NEW. |
| | CLARIFY. |
| | 16) SHOW ALL THE GREASE TRAPS AND PIPE SIZING ON THE |
| | SANITARY RISER. WPB AMEND. TO 2010 FBC SEC. |
| | 107.3.5.1.3. |
| | 17) SHT. P0.1 - THERE ARE CALCULATIONS FOR THE GREASE |
| | INTERCEPTORS BASED ON THE PDI G101 STANDARD AND ALSO ON |
| | THE FL. ADMIN. CODE RULE 64E-6. THE F.A.C. 64E-6 IS FOR |
| | GRAVITY TYPE INTERCEPTORS AND THE PDI G101 IS FOR THE |
| | HYDROMECHANICAL TANKS WHICH ARE ON THE PLANS. YOU |
| | CANNOT USE BOTH.CLARIFY. |
| | 18) SHT. P0.1 - CHECK YOUR FLOW THROUGH CALCULATIONS. I |
| | CALCULATE 95.08 GPM. |
| | 19) SHT. P0.1 - IN THE FLOW THROUGH (GPM) CALCULATIONS, |
| | THE TOTAL GPM HAS BEEN MULTIPLIED BY 24. WHERE IS THIS |
| | NUMBER FROM? CLARIFY. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |