| 2015-06-11 16:57:56 | 2224 PALM BEACH LAKES BOULEVARD |
| | PERMIT #15060045 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE ONLY SHEET SIGNED/SEALED BY THE DESIGN |
| | PROFESSIONAL(S) IS THE COVER SHEET. |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE |
| | EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW (SUCH |
| | AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| | IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | CONFIRM ALL EXIT DOORS AND EXIT GATES ARE EQUIPPED WITH |
| | PANIC HARDWARE. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.FOR ISSUANCE |
| | OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF |
| | THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE |
| | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR |
| | ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER |
| | FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| | |
| | TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS |
| | WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE |
| | FOLLOWING: |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| | PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN |
| | TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE |
| | PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE |
| | PROVIDED AS REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | SHEET P1.1: DRAWING INDICATES SPRINKLER RISER AND |
| | NATURAL GAS LINES RUN INTO AND THROUGH ELECTRICAL ROOM. |
| | |
| | SHEET P1.1: FIRE PIT IS NOT APPROVED AT THIS TIME. |
| | ADDITIONAL INFORMATION IS NEEDED TO SHOW COMPLIANCE |
| | WITH NFPA 1. IS THIS AN ENCLOSED FLAME WITH A LISTED |
| | PIECE OF EQUIPMENT OR AN OPEN FLAME. |
| | |
| | DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT |
| | RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| | 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| | VIOLATIONS OF THIS CODE. |
| | |