| 2015-06-05 18:04:43 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060045 |
| | ADD: 2224 PALM BEACH LAKES BLVD. |
| | CONT: TBD/ TO BE DETEMINED |
| | TEL: ( 305)710-1118 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JUNE 06/2015 |
| | ACTION: DENIED |
| | |
| | 1) THIS BUILDING WILL NEED TO HAVE A RESIDENT INSPECTOR |
| | ON SITE. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO |
| | THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE |
| | CALLED FOR BY ANY PROVISION OF THE TECHNICAL CODES |
| | SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE SAME ARE |
| | IN WRITING AND CERTIFIED BY A RESPONSIBLE OFFICER OF |
| | SUCH SERVICE. THE BUILDING OFFICIAL MAY REQUIRE THE |
| | OWNER TO EMPLOY AN INSPECTION SERVICE IN THE FOLLOWING |
| | INSTANCES: (2) . FOR ALL MAJOR STRUCTURAL ALTERATIONS. |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| | SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| | COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| | WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| | ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| | SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| | CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| | IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| | ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | RESIDENT INSPECTOR FORMS WERE E-MAILED TO |
| | ;[email protected] |
| | RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES |
| | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. |
| | |
| | FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| | KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| | |
| | NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. |
| | FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT |
| | LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 2) ) COVERSHEET INDICATES THIS TO BE A TYPE VB BUILDING |
| | TYPE, WITH 11,482 SQ. FT., PLEASE PROVIDE WHICH |
| | INCREASES WERE TAKEN SINCE FBC-B T-503 ONLY ALLOWS |
| | 6,000 SQ. FT. FOR THIS BUILDING TYPE FBC-B SECTION |
| | BUILDING MODIFICATIONS. |
| | 3) COVERSHEET & LS1.01INDICATE THE OCCUPANT LOAD TO BE |
| | 329 OCCUPANTS, PLEASE PROVIDE THE SQUARE FOOT BREAK |
| | DOWN OF THE OCCUPANT LOAD PER FBC-B TABLE 1004.1.1 FOR |
| | THE A2 SEATING AREAS, BAR AREA FRONT AND BACK, |
| | INTERACTIVE GAME AREA, KITCHEN, STORAGE AND OFFICE |
| | AREAS. FBC-B 1004.1.1 DOES NOT ALLOW YOU TO ROLL DOWN |
| | FRACTION OF OCCUPANTS. |
| | 4) THE LS1.01 SHEET INDICATES DOORS IN A MEANS OF |
| | EGRESS DO NOT REQUIRE PANIC HARDWARE SERVING MORE THAN |
| | 100 OCCUPANTS. PLEASE REFER TO FBC-B 1008.1.10. DOORS |
| | SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR |
| | MORE IN AN A OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| | LOCK OR LATCH UNLESS IT IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | 5) LS1.01 HAS A NOTE THAT FIRE ALARM DRAWINGS SHALL BE |
| | REQUIRED PRIOR TO THE GC STARTS WORK. SECTION 907.2.1 |
| | DOES REQUIRE A FIRE ALARM FOR AN A2 ASSEMBLY OCCUPANCY |
| | WHEN THERE IS A OCCUPANT LOAD OF 300 OR MORE. NOTE A |
| | SEPARATE PERMIT IS REQUIRED WITH DRAWINGS. |
| | 6) THE COVERSHEET NOTES THAT NEW EXTERIOR GLAZING |
| | SYSTEMS, STOREFRONT WINDOWS AND DOORS WILL BE PART OF |
| | THIS PROJECT. PLEASE SHOW COMPLIANCE WITH: COMPONENTS & |
| | CLADDING |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS, & ROOF TOP EXHAUST FANS |
| | |
| | PLEASE NOTE IF THE BUILDING WIND DESIGN CRITERIA IS |
| | CORRECT AND ASSOCIATED PRESSURES THE PRODUCT APPROVALS |
| | CAN BE A DEFERRED SUBMITTAL IS THE DESIGN PROFESSIONAL |
| | AND OR CONTRACTOR INDICATES SUCH IN A WRITTEN RESPONSE. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,? |
| | |
| | 8) THE STRUCTURAL SHEET S-1 GRIDLINE ?L? SHOWS A NEW |
| | ADDITION TO THE BUILDING BUT THERE WAS NO SOILS REPORT |
| | SUBMITTED, PLEASE SHOW COMPLIANCE WITH 2010 FBC-B |
| | 1803.5.2 QUESTIONABLE SOILS. |
| | |
| | 9) THIS SUBMITTAL THERE WAS NO DOCUMENTATION SUBMITTED |
| | AS TO HOW THE LEVEL 3 ALTERATION IS GOING TO COMPLY |
| | WITH THE 2010 FBC-ENERGY 103.2.1. |
| | |
| | 10) SHEET S3 INDICATES A DETAIL ?C? ON SHEET S3 MISSING |
| | ONLY DETAIL IS SECTION A. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. THE FAR RIGHT OF THE DETAIL |
| | SHOWN AT ELEVATION 13 FEET THE TIE DOWN INFORMATION IS |
| | NOT SHOWN. |
| | |
| | 11) SHEET S3-5 SHOW VARIOUS COLUMNS WITH EITHER OR BOTH |
| | THE BOTTOM PLATE AND TOP PLATE BEING WELDED, THERE IS |
| | NO WELD INFORMATION ON THE PLANS AS TO TYPE OF WELD NOR |
| | THE SIZE OF THE WELD. FBC-B 2204.1. |
| | |
| | 12) SHEET S-4 DETAIL C IS MISSING THE ANCHORING OF THE |
| | BAR JOIST AND 2 X 6 RAFTERS TO THE W8X60 STEEL BEAM |
| | THIS IS PART OF THE MWFRS (MAIN WIND FORCE RESISTING |
| | SYSTEM). |
| | |
| | 13) SHEET S-6 COMPONENTS AND CLADDING PRESSURES ARE LOW |
| | FOR ZONES 4 & 5. FBC-B 1609.1.5 / 1609.1.2.3.2. |
| | |
| | 14) SHEET # 3 FROM CAPTIVE AIR BY BUCHNANAN P. E. |
| | CONSULTING ENGINEER DOES SHOW ROOF TOP CURBS AND ROOF |
| | TOP EXHAUST FANS, NO DESIGN FOR ANCHORING OF SYSTEMS, |
| | AND NO FLORIDA PRODUCT APPROVAL SUBMITTED OR LISTED FOR |
| | THESE UNITS, THE PLANS ARE NOT SIGNED NOR SEALED BY A |
| | FLORIDA P.E. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS. |
| | |
| | 15) SHEETS A1.01 & A2.02 DOORS IDENTIFIED AS MARK 4-7 |
| | ARE GLAZED ROLL-UP OVERHEAD DOORS. PLEASE SHOW HOW |
| | COMPLIANCE WITH FBC-B SECTION 2405.2 ALLOWABLE GLAZING |
| | MATERIALS AND LIMITATIONS. |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |