Plan Review Notes
Plan Review Notes For Permit 15060013
Permit Number 15060013
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-07 15:44:08ITEMS REQUESTED IN INITIAL ELECTRICAL PROVISO HAVE NOT
 BEEN COMPLIED WITH. COMPLY WITH COMMENTS LISTED BELOW:
  
 1) RECESSED LIGHTS. REQUIRES THAT RECESSED LUMINAIRES
 BE SEALED, AIR TIGHT, IC RATED. 2010 FBC 402.4.5
  
 2) PROVIDE THE ARC FAULT CALCULATION TO INDICATE THE
 AIC RATING ON SERVICE SWITCHGEAR. NEC 110.9 AND 110.10
  
 3) PROVIDE CUT SHEETS ON INFLOOR UP LIGHTS AND DROP
 DOWN SCREENS TO INDICATE COMPLIANCE WITH THE NEC 110.3
 INCLUDE MANUFACTURER PRODUCT INFORMATION ON LIGHTING
 CONTROL SYSTEM.
  
 4) NEW RECEPTACLES MUST BE TAMPER RESISTANT. THOSE
 OUTLETS IN WET LOCATIONS SHALL BE GFI & WEATHER
 RESISTANT NEC 406.8(B), 406.11
  
 5) INDICATE CIRCUITRY AND DISCONNECTS REQUIERD FOR
 TANKLESS WATER HEATERS.
  
 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATOR. SWIMMING POOL, SECURITY AND
 AUDIO/VIDEO,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]