| Plan Review Notes For Permit 15060013 |
| Permit Number |
15060013 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-07 15:44:08 | ITEMS REQUESTED IN INITIAL ELECTRICAL PROVISO HAVE NOT | | | BEEN COMPLIED WITH. COMPLY WITH COMMENTS LISTED BELOW: | | | | | | 1) RECESSED LIGHTS. REQUIRES THAT RECESSED LUMINAIRES | | | BE SEALED, AIR TIGHT, IC RATED. 2010 FBC 402.4.5 | | | | | | 2) PROVIDE THE ARC FAULT CALCULATION TO INDICATE THE | | | AIC RATING ON SERVICE SWITCHGEAR. NEC 110.9 AND 110.10 | | | | | | 3) PROVIDE CUT SHEETS ON INFLOOR UP LIGHTS AND DROP | | | DOWN SCREENS TO INDICATE COMPLIANCE WITH THE NEC 110.3 | | | INCLUDE MANUFACTURER PRODUCT INFORMATION ON LIGHTING | | | CONTROL SYSTEM. | | | | | | 4) NEW RECEPTACLES MUST BE TAMPER RESISTANT. THOSE | | | OUTLETS IN WET LOCATIONS SHALL BE GFI & WEATHER | | | RESISTANT NEC 406.8(B), 406.11 | | | | | | 5) INDICATE CIRCUITRY AND DISCONNECTS REQUIERD FOR | | | TANKLESS WATER HEATERS. | | | | | | 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR GENERATOR. SWIMMING POOL, SECURITY AND | | | AUDIO/VIDEO, | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] |
|