Plan Review Notes
Plan Review Notes For Permit 15051314
Permit Number 15051314
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-17 09:35:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15051314
 ADD: 400 N. FLAGLER DR. SUITE # 703
 CONT: CUSTOM CONSTRUCTION
 TEL: (561)670-0779
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JUNE 17/2015
 ACTION: DENIED
  
 1A) SEMI-COMPLIED. THE PRODUCT APPROVALS HAVE NOT BEEN
 REVIEWED BY THE DESIGNER OF RECORD AS FAR AS PRESSURES.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 1B) THE CONCERN IS WITH THE EASTERN FD 8100 SLIDING
 GLASS DOOR SYSTEM PAGE 4 OF 6 IN THE PRODUCT APPROVAL
 THE DESIGN PRESSURE IS +/- 60 PSF FOR AN OPENING SIZE
 OF 240 IN. X 120 IN. PLEASE HAVE EASTERNS ENGINEER
 PROVIDE A RATIONAL ANALYSIS FOR THE PRESSURES FOR THE
 VAROIUS SIZE OPENINGS. FOR SMALLER OPENINGS THE
 PRESSURES RISE AS WELL AS THE POSITIVE PRESSURES, THE
 BUILDING IS A 23 STORY HIGH RISE IN AN EXPOSURE D.
 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS
 FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL
 ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE
 WITH THIS CODE.THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS THAT PROVIDE
 SUPPORTING DOCUMENTATION THAT THE PROPOSED PENETRATION
 AND OPENING DETAILS DESCRIBED IN THE CONSTRUCTION
 DOCUMENTS MAINTAIN THE WEATHER RESISTANCE OF THE
 EXTERIOR WALL ENVELOPE. THE SUPPORTING DOCUMENTATION
 SHALL FULLY DESCRIBE THE EXTERIOR WALL SYSTEM WHICH WAS
 TESTED, WHERE APPLICABLE, AS WELL AS THE TEST PROCEDURE
 USED.
  
 2) COMPLIED. FLOOR INSULATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  