| 2015-07-17 09:35:26 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15051314 |
| | ADD: 400 N. FLAGLER DR. SUITE # 703 |
| | CONT: CUSTOM CONSTRUCTION |
| | TEL: (561)670-0779 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. JUNE 17/2015 |
| | ACTION: DENIED |
| | |
| | 1A) SEMI-COMPLIED. THE PRODUCT APPROVALS HAVE NOT BEEN |
| | REVIEWED BY THE DESIGNER OF RECORD AS FAR AS PRESSURES. |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | |
| | 1B) THE CONCERN IS WITH THE EASTERN FD 8100 SLIDING |
| | GLASS DOOR SYSTEM PAGE 4 OF 6 IN THE PRODUCT APPROVAL |
| | THE DESIGN PRESSURE IS +/- 60 PSF FOR AN OPENING SIZE |
| | OF 240 IN. X 120 IN. PLEASE HAVE EASTERNS ENGINEER |
| | PROVIDE A RATIONAL ANALYSIS FOR THE PRESSURES FOR THE |
| | VAROIUS SIZE OPENINGS. FOR SMALLER OPENINGS THE |
| | PRESSURES RISE AS WELL AS THE POSITIVE PRESSURES, THE |
| | BUILDING IS A 23 STORY HIGH RISE IN AN EXPOSURE D. |
| | 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS |
| | FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL |
| | ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE |
| | WITH THIS CODE.THE CONSTRUCTION DOCUMENTS SHALL INCLUDE |
| | MANUFACTURER?S INSTALLATION INSTRUCTIONS THAT PROVIDE |
| | SUPPORTING DOCUMENTATION THAT THE PROPOSED PENETRATION |
| | AND OPENING DETAILS DESCRIBED IN THE CONSTRUCTION |
| | DOCUMENTS MAINTAIN THE WEATHER RESISTANCE OF THE |
| | EXTERIOR WALL ENVELOPE. THE SUPPORTING DOCUMENTATION |
| | SHALL FULLY DESCRIBE THE EXTERIOR WALL SYSTEM WHICH WAS |
| | TESTED, WHERE APPLICABLE, AS WELL AS THE TEST PROCEDURE |
| | USED. |
| | |
| | 2) COMPLIED. FLOOR INSULATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |