| | PROJECT: GIBB RENNOVATION |
| | PERMIT#: 15051314 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) CHANGE THE "CODE" NOTE ATE THE BOTTOM RIGHT ON SHEET |
| | 1 TO READ THE 2008 EDITION OF THE NFPA 70 (NEC) |
| | NATIONAL ELECTRICAL CODE. |
| | |
| | 2) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| | SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| | OUTLET. NEC 210.52 |
| | |
| | 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| | PROTECTED. NEC 210.12 |
| | |
| | 4) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | 5) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE |
| | BATHROOMS. NEC 210.11 (C) |
| | |
| | 6) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. PROVIDE THE OCPD AND |
| | CORRESPONDING WIRE SIZE FOR NEC 408.4 |
| | |
| | 7) RECESSED LUMINAIRES INSTALLED IN THE BUILDING |
| | THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | UNCONDITIONED SPACES. FBC-E 502.3.8 RECESSED LIGHTING. |
| | |
| | 8) INDICATE OR VERIFY THE INSTALLATION OF SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. |
| | |
| | 9))BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL |
| | BE USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC |
| | 314.27(C) |
| | |
| | 10) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED |
| | IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. NEC 210.52 (D) |
| | |
| | 11) PROVIDE A LIGHTING FIXTURE SCHEDULE TO IN CLUDE THE |
| | UNDER CABINET LIGHTING MENTIONED IN THE NOTE ON SHEET |
| | 1. ALL LIGHTING TO BE IN COMPLIANCE WITH THE FBC-E, NEC |
| | 410, AND NEC 110.3 |
| | |
| | 12) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST |
| | HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC |
| | 210.52(E)(3). |
| | |
| | 13) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR FIRE ALARM, FIRE SPRINKLER, SECURITY, |
| | CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |