| 2015-06-22 08:44:51 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15051314 |
| | ADD: 400 N. FLAGLER DR. SUITE # 703 |
| | CONT: CUSTOM CONSTRUCTION |
| | TEL: (561)670-0779 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 22/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET # 1 INDICATES NEW SLIDDING GLASS DOORS AND THE |
| | EXPOSURE GIVEN IS A C EXPOSURE. THIS EXPOSURE IS |
| | CONSIDERED A D EXPOSURE 2010 FBC-B 1609.4.3. PLEASE |
| | PROVIDE THE PRESSURES FOR THE 240 FT. HIGH, HIGH RISE |
| | IN EXPOSURE D. THE UNKNOWN VARIABLE IS THIS UNIT IN A |
| | WALL ZONE 4 OR A WALL ZONE 5, A END ZONE? |
| | |
| | 2) THE PLANS ALSO INDICATE THE REMOVAL OF FLOOR |
| | COVERINGS AND THE USE OF SAM 3 90, PLEASE SUBMIT THE |
| | ACTUAL TEST REPORTS FOR THIS PRODUCT AND FOR THE FLOOR |
| | THICKNESS AT 6 INCHES, UNLESS VERIFIED BY AN ENGINEER. |
| | THE TEST REPORTS NEED TO BE APPROVED TO: |
| | |
| | 2FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |