2015-06-04 11:46:241ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE INSTALLATION OF A NEW AC SYSTEM TO CONDITION THE
 PREVIOUSLY UNCONDITIONED GARAGE, RESULTS WITH THE
 GARAGE NOW BEING CLASSIFIED AS AN ADDITION- SEE TABLE
 101.4.1 AND SECTION 202 (DEFINITIONS) FBC-10 ENERGY
 CONSERVATION.
 FULL COMPLIANCE AS A HABITABLE SPACE IS REQUIRED IN
 ACCORDANCE WITH BOTH THE FBC-10 RESIDENTIAL, AND
 CHAPTER 4 OF THE FBC-10 ENERGY. PROVIDE PLANS AND
 SPECIFICATIONS, AND SUBMIT EITHER ENERGY EFFICIENCY
 FORM 402-2010 OR FORM 405-2010. THE NEW PLAN SHALL
 INDICATE THE PROPOSED USE OF THE GARAGE- PLEASE NOTE
 IMPACT FEES MAY APPLY.
 2) AS THE PERRMIT APPLICATION INDICATES THIS IS A NEW
 SYSTEM, PLEASE DISCARD THE AC REPLACEMENT FORM: IT IS
 NOT VALID FOR THIS PROJECT.
 3) PROVIDE AC LOAD CALCULATIONS FOR THE NEW SYSTEM IN
 ACCORDANCE W ACCA MANUAL J- SECTION 403.6.1 FBC-10
 ENERGY.
 4) PROVIDE ON THE NEW AC PLAN THE FOLLOWING: A) THE
 LOCATIONS OF THE AIR HANDLER AND CONDENSER. (SHOW THE
 DISCONNECT LOCATIONS FOR EACH AND PROVIDE ELECTRICAL
 PLANS.) B) CONDENSATE DISPOSAL DETAILS. C) CONDENSER
 PAD AND ANCHORING DETAILS- SEE SECTION M1307.2.1 FBC-10
 RES.
  