| Plan Review Notes For Permit 15051296 |
| Permit Number |
15051296 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-08 07:41:28 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR | | | THE PROPOSED AC SYSTEM IN ACCORDANCE WITH ACCA MANUAL N | | | OR THE ACCA/ASHRAE STANDARD 183- SECTION 503.2.1 FBC-10 | | | ENERGY CONSERVATION. | | | 2) SHEET A3: THE PLAN IS INDICATING THE AREA ABOVE THE | | | CEILING IS A RETURN AIR PLENUM. REFERENCE SECTION | | | 602.2.1 AND ALL APPLICABLE SUB-SECTIONS PERTAINING TO | | | NON-COMBUSTIBLE AND OTHER MATERIALS PERMITTED TO BE | | | INSTALLED IN THE PLENUM. PLEASE PLACE NOTES ON THE PLAN | | | TO VERIFY COMPLIANCE. | | | 3) A3: INDICATE THE TYPE AND SIZE OF CONDENSATE PIPING | | | AND CLARIFY THE DISCHARGE LOCATION- SECTION 307. THERE | | | IS A NOTE ON THE PLAN STATING "PROVIDE COND. TO WET | | | COL.": PLEASE CLARIFY IF THIS IS AN EXISTING STORM | | | DRAIN RISER. | | | 4) A3: PROVIDE UPDATED WIND LOAD TIE-DOWN ENGINEERING | | | FOR ANCHORING THE CONDENSER TO THE PAD. THE DETAIL ON | | | THE PLAN IS INDICATING A WIND SPEED OF 120 MPH. | | | REFERENCE SECTION 301.12 FBC-10 MECHANICAL, AND SECTION | | | 1609 FBC-10 BUILDING. THE ULTIMATE DESIGN WIND SPEED | | | FOR RISK CATEGORY II IN WEST PALM BEACH IS 170 MPH- SEE | | | FIGURE 1609A. REVISE THE DETAIL ACCORDINGLY AND | | | INDICATE THE TYPE, SIZE, AND GAGE OF STEEL HURRICANE | | | STRAPS TO BE INSTALLED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|