| 2015-09-10 19:10:58 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ENERGY FORM DOES NOT SHOW COMPLIANCE WITH FBC |
| | ENERGY CONSERVATION SECTION 402. THE U-FACTOR SPECIFIED |
| | IS MORE THAN THE MAXIMUM OF .65. THE PERCENTAGE OF |
| | GLASS TO FLOOR AREA IS NOT 20 PERCENT. THE RAISED FLOOR |
| | AREA IS SPECIFIED AS 56 SQFT AND THE ENCLOSED AREA IS |
| | 177 SQFT. THE AHU LOCATION IS NOT LISTED ON THE FORM. |
| | THE FORM IS NOT SIGNED BY THE OWNER/AGENT. YOU WILL |
| | NEED TO SUBMIT DOCUMENTATION FOR THE WINDOWS THAT WILL |
| | BE INSTALLED TO SHOW THEIR U-FACTOR AND SHGC. |
| | |
| | 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW |
| | WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING |
| | BY THE DESIGNER OF RECORD. FBC107.3.4.1 |
| | |
| | 3) SHOW THAT THE WINDOWS WILL COMPLY WITH R301.2.1.2 |
| | PROTECTION OF OPENINGS. WINDOWS IN BUILDINGS LOCATED IN |
| | WINDBORNE DEBRIS REGIONS SHALL HAVE GLAZED OPENINGS |
| | PROTECTED FROM WINDBORNE DEBRIS. GLAZED OPENING |
| | PROTECTION FOR WINDBORNE DEBRIS SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM E 1996, |
| | ASTM E 1886, SSTD 12 OR TAS 201,202 AND 203 OR AAMA 506 |
| | REFERENCED THEREIN. ( IF USING STORM PANELS, SUBMIT |
| | PRODUCT APPROVALS AND AN INSTALLATION SCHEDULE. ) |
| | |
| | 4) THE VALUE OF $10,000.00 ON THE APPLICATION FOR THE |
| | SCOPE OF WORK SHOWN ON THE PLANS APPEARS TO |
| | UNDERVALUED. SUBMIT A COPY OF THE SIGNED CONTRACT. FBC |
| | 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. SUBMIT |
| | A COPY OF THE SIGNED CONTRACT TO VERIFY THE VALUATION |
| | OF THE PROJECT. |
| | |
| | 5) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | |