Plan Review Notes
Plan Review Notes For Permit 15051275
Permit Number 15051275
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-02 09:46:236/2/2015
 PROJECT: SOLAR EATER HEATER
 PERMIT#: 15051275
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE PLANS DO NOT SHOW THAT THE PUMP IS A PLUG IN
 UNIT. PROVIDE THE MANUFACTURER DOCUMENTATION ON THE
 PUMP. INDICATE ON THE PLAN IF THERE IS AN EXISTING
 RECEPTACLE FOR THE PUMP TO PLUG INTO. IF NOT REVISE THE
 PLAN TO INDICATE REQUIRED RECEPATCLE OUTLET(S). A
 SEPARATE ELECTRIC PERMIT IS REQUIRED FOR THE
 INSTALATION OF ANY ELECTRICAL CIRCUITRY THAT IS
 REQUIRED AND NOT CURRENTLY EXISTING TO REMAIN. WPB
 AMEND. TO 2010 FBC SEC.107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  