| 2015-06-05 11:09:46 | 6/5/2015 |
| | PROJECT: WESMINSTER RESIDENCE |
| | PERMIT#: 15051158 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) THE ELECTRICAL PLAN INDIACTES VIA NOTES ON A.01 THAT |
| | THE ELECTRICAL PANEL CERTAIN LIGHTING AND SMOKE |
| | DETECTORS WILL REMAIN FOR THE DURATION OF THE |
| | CONSTRUCTION PROCESS. INDICATE THE LOCATION OF THE |
| | ELECTRICAL PANEL, ELECTRICAL SERVICE, LIGHTING AND |
| | SMOKE DETECTORS THAT ARE EXISTING TO REMAIN. |
| | |
| | 2) PROVIDE A PANEL SCHEDULE FOR CIRCUITS THAT WILL |
| | REMAIN. NEC 408.4 |
| | |
| | 3) INDICATE THE LOCATION OF THE REQUIRED GFI |
| | RECEPTACLES FOR CONSTRUCTION. NEC 590.6 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |