| Plan Review Notes For Permit 15051140 |
| Permit Number |
15051140 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-12-08 07:19:42 | 4TH REVIEW 2014 MECHANICAL | | | PERMIT #15051140 | | | 12/8/15 | | | | | | 1) I HAVE REMOVED THE AC CHANGEOUT FORMS AND AHRI | | | CERTIFICATES FROM THE SUBMITTAL PACKAGE FOR THIS | | | PROJECT PER ARCHITECT JAIMES PAINE'S DIRECTION- THEY | | | ARE NOT RELEVANT TO THE PROPOSED PROJECT. | | | 2) PLEASE PROVIDE ENERGY CALCULATIONS AND AC COOLING | | | AND HEATING CALCULATIONS FOR UNITS 412A AND 414A. THESE | | | ARE THE TWO MAIN BUILDINGS WITH THE 16 SEER RHEEM AC | | | SYSTEMS- THE CALCULATIONS FOR THE REAR RENTAL UNITS | | | 412B AND 414B HAVE BEEN SUBMITTED AND ARE APPROVED FOR | | | THE AC INSTALLATIONS. | | | 3) SHOW THE LOCATIONS OF THE THE REAR BUILDING | | | CONDENSER UNITS AND PROVIDE INSTALLATION DETAILS. | | | PLEASE NOTE THAT ALL EXTERIOR CONDENSERS SHALL BE | | | INSTALLED AT OR ABOVE THE FLOOD ELEVATION HEIGHT AS | | | REQUIRED BY SECTION 1612.4 FBC-10 BUILDING. | | | 4) PROVIDE THE DIMENSIONS OF THE TRANSFER GRILLS IN | | | UNITS 412A AND 412B. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|