Plan Review Notes
Plan Review Notes For Permit 15051140
Permit Number 15051140
Review Stop M
Sequence Number 4
Notes
Date Text
2015-12-08 07:19:424TH REVIEW 2014 MECHANICAL
 PERMIT #15051140
 12/8/15
  
 1) I HAVE REMOVED THE AC CHANGEOUT FORMS AND AHRI
 CERTIFICATES FROM THE SUBMITTAL PACKAGE FOR THIS
 PROJECT PER ARCHITECT JAIMES PAINE'S DIRECTION- THEY
 ARE NOT RELEVANT TO THE PROPOSED PROJECT.
 2) PLEASE PROVIDE ENERGY CALCULATIONS AND AC COOLING
 AND HEATING CALCULATIONS FOR UNITS 412A AND 414A. THESE
 ARE THE TWO MAIN BUILDINGS WITH THE 16 SEER RHEEM AC
 SYSTEMS- THE CALCULATIONS FOR THE REAR RENTAL UNITS
 412B AND 414B HAVE BEEN SUBMITTED AND ARE APPROVED FOR
 THE AC INSTALLATIONS.
 3) SHOW THE LOCATIONS OF THE THE REAR BUILDING
 CONDENSER UNITS AND PROVIDE INSTALLATION DETAILS.
 PLEASE NOTE THAT ALL EXTERIOR CONDENSERS SHALL BE
 INSTALLED AT OR ABOVE THE FLOOD ELEVATION HEIGHT AS
 REQUIRED BY SECTION 1612.4 FBC-10 BUILDING.
 4) PROVIDE THE DIMENSIONS OF THE TRANSFER GRILLS IN
 UNITS 412A AND 412B.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  