| 2015-10-07 12:38:47 | 3RD REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15051140 | | | 10/7/15 | | | | | | 1) THE SUBMITTED ENERGY AND AC COOLING AND HEATING | | | CALCULATIONS INDICATE 18-SEER 1.5- TON TRANE SYSTEMS | | | FOR UNITS 412 AND 414, HOWEVER THE PLANS INDICATE | | | 13-SEER 2-TON RHEEM SYSTEMS. IN ADDITION TWO AC | | | CHANGEOUT FORMS FOR UNIT 414 HAVE BEEN SUBMITTED | | | SPECIFYING A NEW 13-SEER 2-TON RUUD SYSTEM TO BE | | | INSTALLED. I AM CONFUSED: PLEASE CORRECT THE PLANS TO | | | MATCH THE SUBMITTED DOCUMENTS, OR VICE-VERSA. PLEASE | | | NOTE THAT NO DOCUMENTS HAVE BEEN SUBMITTED FOR THE NEW | | | MINI-SPLIT SYSTEMS SHOWN IN THE REAR BUILDING 1ST AND | | | 2ND FLOOR, IF THESE ARE NEW SYSTEMS (NOT REPLACED) | | | ENERGY AND AC LOAD CALCULATIONS ARE REQUIRED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|