2015-10-07 12:38:473RD REVIEW: FBC 2010 MECHANICAL
 PERMIT #15051140
 10/7/15
  
 1) THE SUBMITTED ENERGY AND AC COOLING AND HEATING
 CALCULATIONS INDICATE 18-SEER 1.5- TON TRANE SYSTEMS
 FOR UNITS 412 AND 414, HOWEVER THE PLANS INDICATE
 13-SEER 2-TON RHEEM SYSTEMS. IN ADDITION TWO AC
 CHANGEOUT FORMS FOR UNIT 414 HAVE BEEN SUBMITTED
 SPECIFYING A NEW 13-SEER 2-TON RUUD SYSTEM TO BE
 INSTALLED. I AM CONFUSED: PLEASE CORRECT THE PLANS TO
 MATCH THE SUBMITTED DOCUMENTS, OR VICE-VERSA. PLEASE
 NOTE THAT NO DOCUMENTS HAVE BEEN SUBMITTED FOR THE NEW
 MINI-SPLIT SYSTEMS SHOWN IN THE REAR BUILDING 1ST AND
 2ND FLOOR, IF THESE ARE NEW SYSTEMS (NOT REPLACED)
 ENERGY AND AC LOAD CALCULATIONS ARE REQUIRED.
  