| 2015-10-08 08:24:30 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15051140 |
| | ADD: 412/ 414 50 TH ST. UNITS A & B |
| | CONT: BMB SOLUTIONS CORP |
| | TEL: (561)503-1415 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. OCT. 08/ 2015 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3A) 3RD REQUEST. WINDOWS AND DOORS IN THE FOOTPRINT OF |
| | THE STAIR (VERTICALLY) REQUIRES 1 HOUR OPENING |
| | PROPECTIVES!!! NO FIRE SHUTTER WAS SUBMITTED FOR 1 HOUR |
| | OR 3/4 HOUR. SHEET A1.1 IT APPEARS THAT THE WINDOWS AND |
| | DOORS ARE BEING REPLACED WITHIN 10 FEET OF THE STAIR |
| | AND LANDING ON BOTH THE FRONT AND REAR BUILDINGS. IT |
| | APPEARS THAT EACH UPPER APARTMENT IS A SINGLE MEANS OF |
| | EGRESS, NO ELEVATIONS PROVIDED TO VERIFY. SINGLE MEANS |
| | OF EGRESS WILL NEED 1 HOUR FIRE SEPARATION,COMPLY UNDER |
| | SECTION FBC-B 1019.2., FBC-B 1026.6 EXC. # 2 & 2007 |
| | FBC-B COMMENTARY FIGURE 1023.6(1) PROTECTION OF |
| | EXTERIOR STAIRWAYS. DOORS AND WINDOWS WITHIN THE |
| | FOOTPRINT OF THE EXTERIOR STAIR REQUIRE 1 HOUR FIRE |
| | RATING AND WINDOWS AND DOORS WITHIN 10 FT. OF THE |
| | LANDINGS AND STAIR REQUIRE 3/4 HR. OPENING PROTECTIVES. |
| | SHOW THE FULL LENGTH OF THE EXTERIOR STAIR AND LANDINGS |
| | TO DETERMINE WHICH OPENINGS REQUIRE A 1 HOUR FIRE |
| | RATING AND WHICH REQUIRE 3/4 HOUR FIRE RATING. |
| | |
| | 3B)2ND REQUEST. NOTE WINDOWS AND DOORS THAT HAVE 3/4 HR |
| | AND OR 1 HOUR FIRE RATING NORMALLY DO NOT HAVE LARGE |
| | MISSILE RESISTANT TESTING AND STORM SHUTTERS WILL NEED |
| | TO BE INSTALLED ON THESE OPENINGS. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION FOR CODE COMPLIANCE: |
| | |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.2. |
| | |
| | FL BLD CODE 2010 SECTION 107.2.5., |
| | 1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 PROCEDURES: A |
| | COMPLETE INSTALLATION SCHEDULE SUMMARIZING & |
| | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING |
| | REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC., |
| | SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO |
| | FACILITATE PLAN REVIEW AND PERMIT ISSUANCE |
| | |
| | 4) SEMI-COMPLIED, 2 DOOR APPROVALS FROM 2 DIFFERENT |
| | MANUFACTURERS, 2 WINDOW PRODUCT APPROVALS FROM 2 |
| | DIFFERENT MANUFACTURERS & 2 MULLION PRODUCT APPROVALS |
| | FROM 2 DIFFERENT MULLION MANUFACTURERS WERE SUBMITTED. |
| | PLEASE IDENTIFY THEIR LOCATION ON THE PLAN WHERE THEY |
| | ARE GOING TO BE INSTALLED. |
| | |
| | 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL ADMINISTRATIVE CODE. |
| | 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | NOTE THE JELD-WEN DOORS NOT REVIEWEDD BY THE DESIGNER |
| | OF RECORD. |
| | TRULITE DOOR SUBMITTAL NO FLORIDA APPROVAL NUMBER NOR |
| | NOA. ONLY ONE COPY. |
| | NO WINDOW REPORT SUBMITTED ONLY THE INTER LAYER OF |
| | DUPONT BUTACITE PVB INTERLAYER NOA 11-0624.01 |
| | NO MULLION REPORT SUBMITTED. |
| | |
| | 5) COMPLIED. PLEASE 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS & MULLIONS IDENTIFY WINDOW SIZES, GLAZING |
| | OPTIONS, MULLION IF REINFORCED, OPTIONS FOR ANCHORING |
| | AND PRESSURES. |
| | (E) SHUTTERS |
| | |
| | 6) 3RD REQUEST THE CONTRACTOR HAS NOT SUBMITTED ANY |
| | TEST REPORTS FOR REVIEW!!!!!!!! SHEET A.2 INDICATES NEW |
| | FLOORING BUT NO INFORMATION ON THE 2ND FLOOR |
| | INSULATION, PLEASE PROVIDE TESTING FOR THE FOLLOWING |
| | (3) CODE SECTIONS: |
| | |
| | NOTE: A UL REPORT WAS SUBMITTED FOR THE REQUIREMENT OF |
| | 1 HOUR FIRE SEPARATION, WITHIN THE REPORT THERE ARE 17 |
| | SUB-SYSTEMS WHICH ARE TO BE INSTALLED? THERE IS ALSO A |
| | USG REPORT SUBMITTED WITH A 1 HOUR FIRE RATING, IF THIS |
| | REPORT IS FOR SOUND IT DOES NOT MEET THE REQUIRED STC & |
| | IIC RATING OF 50. |
| | |
| | 6A) 2ND REQUEST. FBC-B 2010 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6B) 2ND REQUEST. FBC-B 2010 1207.2 1207.2 AIR-BORNE |
| | SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 6C) 2ND REQUEST. TYPE III-TYPE V CONSTRUCTION: |
| | 719.2 CONCEALED INSTALLATION. INSULATING MATERIALS, |
| | WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE |
| | OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 10/13/2015 PICTURES SENT BY E-MAIL FROM THE CONTRACTOR |
| | INDICATE WHAT APPEARS TO BE A 2ND EXTERIOR STAIR NOT |
| | SHOWN ON THE PLANS THAT APPEARS TO HAVE BEEN |
| | UNPERMITTED WORK. THIS STAIR MUST BE REMOVED, THE |
| | HANDRAIL / GUARDRAIL SYSTEM IS NOT IN COMPLIANCE WITH |
| | THE CODE, FOR A R2 UNIT. THE SECOND ISSUE IS WITH THE |
| | STAIR UPPER LANDING ENDING WITH THE ROOF TOP FLAT DECK, |
| | THIS MAKES THIS AREA LIVEABLE SPACE, NEED TO PROVIDE |
| | LIVE LOADS FOR ROOF DECK AND SIZE AND SPAN FOR ROOF |
| | JOIST. REMOVE STAIRS OR MAKE CODE COMPLIANT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |