2015-09-08 10:04:542ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15051140
 9/8/15
  
 1) AC CHANGE OUT COMPLIANCE FORMS: PLEASE SUBMIT TWO
 FORMS FOR UNIT 412, AND TWO FORMS FOR UNIT 414 AS SHOWN
 ON THE AC PLANS, AND MATCH THE MAKE OF THE REPLACED AC
 SYSTEMS WITH THE MAKE LISTED ON THE PLANS.
 2) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PLEASE
 SUBMIT AHRI CERTIFICATES FOR THE REPLACEMENT AC
 SYSTEMS.
 3) REFER TO SECTION 403.2.4 FBC-10 ENERGY CONSERVATION
 AND PLACE NOTES ON THE PLAN ACCORDINGLY TO VERIFY
 COMPLIANCE: 403.2.4 AIR-HANDLING UNITS.
 AIR HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER,
 EFFICIENT, AND ECONOMIC OPERATION OF THE
 AIR-CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR
 MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM
 IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A
 DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN
 IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT
 THE SYSTEM DOWN WHEN THE CONDENSATION DRAIN IS NOT
 WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO
 AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU
 ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE
 EACH SEASON OF PEAK OPERATION.
  