| 2015-11-05 17:55:02 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 FBC, |
| | (FLORIDA BUILDING CODE) AS APPLICABLE AND BELOW ARE THE |
| | DEFICIENCIES NOTED. |
| | |
| | 1. NEC 210.52(E)(2) THERE SHALL BE AN EXTERIOR GFI |
| | OUTLET FOR EACH GRADE LEVEL UNIT. |
| | 2. NEC 210.63 THERE SHALL BE A SERVICE OUTLET WITHIN |
| | 25? OF EACH OF THE CONDENSING UNITS. |
| | 3. NEC 210.70(A)(2)(A) PERMITS AUTOMATIC CONTROL FOR |
| | ILLUMINATION OF EXTERIOR STAIRWAYS. |
| | 4. NEC 215.5 YOU SHALL PROVIDE A SITE SPECIFIC FEEDER |
| | DIAGRAM SHOWING FEEDER DETAILS, CONDUCTOR SIZING AND |
| | LOAD CALCS. IN ADDITION TO THE TYPICAL UNIT CALCS, |
| | CALCS FOR THE COMPLETE SERVICE SHALL BE PROVIDED. |
| | 5. NEC 300.5(B) WIRING CONDITIONS DICTATE CONDUCTOR |
| | INSULATION. YOUR NOTE 5 CALLS FOR THHN. NOTE: THAT IS |
| | NOT ACCEPTABLE FOR WET LOCATIONS. |
| | 6. NEC 314.27 HAS SPECIFIC WEIGH REQUIREMENTS FOR |
| | CEILING LUMINAIRE OUTLETS AND PADDLE FAN OUTLETS. |
| | 7. NEC 406.8(B) RECEPTACLES INSTALLED OUTDOORS IN |
| | ADDITION TO THE IN-USE TYPE COVERS, SHALL BE LISTED |
| | ?WR? WEATHER RESISTANT. |
| | 8. FBC-R 302.4.1 REQUIRES THAT ALL PENETRATIONS OF FIRE |
| | RESISTANCE RATED WALL OR FLOOR ASSEMBLIES BE PROTECTED |
| | BY AN APPROVED FIRESTOP SEALING SYSTEM. INDICATE HOW |
| | THE FEEDERS TO THE UPPER LEVEL PANELS WILL BE RUN. |
| | 9. FBC-R 302.13 REQUIRES MINIMUM OF 3? CLEARANCE FROM |
| | COMBUSTIBLE INSULATION FOR RECESSED LIGHTING. |
| | 10. FBC-R 303.6 ALL EXTERIOR STAIRWAYS SHALL BE |
| | PROVIDED WITH A MEANS TO ILLUMINATE THE STAIRS, |
| | INCLUDING THE LANDINGS AND TREADS. |
| | 11. FBC-E 402.4.5 RECESSED LIGHTING INSTALLED IN THE |
| | BLDG.?S THERMAL ENVELOPE SHALL BE IC RATED AND SEALED |
| | TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | NON-CONDITIONED SPACE. |
| | 12. FBC-E 404 A MINIMUM OF 50% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICIENCY LAMPS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |