Plan Review Notes
Plan Review Notes For Permit 15051140
Permit Number 15051140
Review Stop E
Sequence Number 2
Notes
Date Text
2015-11-05 17:55:02THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 FBC,
 (FLORIDA BUILDING CODE) AS APPLICABLE AND BELOW ARE THE
 DEFICIENCIES NOTED.
  
 1. NEC 210.52(E)(2) THERE SHALL BE AN EXTERIOR GFI
 OUTLET FOR EACH GRADE LEVEL UNIT.
 2. NEC 210.63 THERE SHALL BE A SERVICE OUTLET WITHIN
 25? OF EACH OF THE CONDENSING UNITS.
 3. NEC 210.70(A)(2)(A) PERMITS AUTOMATIC CONTROL FOR
 ILLUMINATION OF EXTERIOR STAIRWAYS.
 4. NEC 215.5 YOU SHALL PROVIDE A SITE SPECIFIC FEEDER
 DIAGRAM SHOWING FEEDER DETAILS, CONDUCTOR SIZING AND
 LOAD CALCS. IN ADDITION TO THE TYPICAL UNIT CALCS,
 CALCS FOR THE COMPLETE SERVICE SHALL BE PROVIDED.
 5. NEC 300.5(B) WIRING CONDITIONS DICTATE CONDUCTOR
 INSULATION. YOUR NOTE 5 CALLS FOR THHN. NOTE: THAT IS
 NOT ACCEPTABLE FOR WET LOCATIONS.
 6. NEC 314.27 HAS SPECIFIC WEIGH REQUIREMENTS FOR
 CEILING LUMINAIRE OUTLETS AND PADDLE FAN OUTLETS.
 7. NEC 406.8(B) RECEPTACLES INSTALLED OUTDOORS IN
 ADDITION TO THE IN-USE TYPE COVERS, SHALL BE LISTED
 ?WR? WEATHER RESISTANT.
 8. FBC-R 302.4.1 REQUIRES THAT ALL PENETRATIONS OF FIRE
 RESISTANCE RATED WALL OR FLOOR ASSEMBLIES BE PROTECTED
 BY AN APPROVED FIRESTOP SEALING SYSTEM. INDICATE HOW
 THE FEEDERS TO THE UPPER LEVEL PANELS WILL BE RUN.
 9. FBC-R 302.13 REQUIRES MINIMUM OF 3? CLEARANCE FROM
 COMBUSTIBLE INSULATION FOR RECESSED LIGHTING.
 10. FBC-R 303.6 ALL EXTERIOR STAIRWAYS SHALL BE
 PROVIDED WITH A MEANS TO ILLUMINATE THE STAIRS,
 INCLUDING THE LANDINGS AND TREADS.
 11. FBC-E 402.4.5 RECESSED LIGHTING INSTALLED IN THE
 BLDG.?S THERMAL ENVELOPE SHALL BE IC RATED AND SEALED
 TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 NON-CONDITIONED SPACE.
 12. FBC-E 404 A MINIMUM OF 50% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICIENCY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  