Plan Review Notes
Plan Review Notes For Permit 15051140
Permit Number 15051140
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-09 11:49:511ST REVIEW: FBC 2010 MECHANICAL
 7/9/15
  
 1) CLARIFY THE SCOPE OF WORK FOR HVAC. IT APPEARS THAT
 AC SYSTEMS REPLACEMENTS ARE PROPOSED IN EACH OF THE
 FOUR UNITS, INCLUDING NEW DUCTWORK IN UNITS 412 AND
 414. PLEASE CONFIRM WITH NOTES ON THE PLAN. PLEASE NOTE
 THAT COOLING AND HEATING CALUCLATIONS, AND ENERGY
 CALCULATIONS ARE REQUIRED FOR ANY PREVIOUSLY
 UNCONDTIONED BUILDINGS THAT ARE NOW BEING CONDITIONED-
 TABLE 101.4.1 AND SECTION 403.6.1 FBC-10 ENERGY
 CONSERVATION.
 2) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS LISTING
 MAKES AND MODELS, COOLING AND HEATING CAPACITES,
 EFFICIENCY RATINGS, AND ELECTRICAL REQUIEMENTS.
 3) SUBMIT AHRI CERTIFICATES FOR EACH NEW AC SYSTEM-
 SECTION 101.4.7 FBC-10 ENERGY CONSERVATION
 4) PROVIDE CONDENSATE DISPOSAL DETAILS FOR EACH SYSTEM-
 TYPE AND SIZE OF PIPING, PIPING RUNS, AND DISCHARGE
 LOCATIONS. INDICATE HOW SECONDARY OR AUXILIARY DISPOSAL
 IS BEING ACCOMPLISHED- SECTION 307.2.3 FBC-10 MECH.
 5) THE PLAN SHOWS AIR HANDLERS IN THE ATTICS OF UNITS
 412 & 414, HOWEVER NO ACCESS IS SHOWN ON THE PLANS- SEE
 SECTIONS 306.3 AND 306.3.2 AND PROVIDE DETAILS
 INDICATING COMPLIANCE WITH ALL REQUIREMENTS.
 6) SHEET 3.1: THE CU MOUNTING DETAIL HAS INCOMPLETE
 DETAILS: PROVIDE THE DEPTH OF ANCHOR EMBEDMENT INTO THE
 SLAB, INDICATE WHICH TIE-DOWN CLIP TO BE INSTALLED, AND
 THE WIND LOAD DESIGN CRITERIA- SECTION 301.12.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  