| 2015-06-22 07:40:29 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15051140 |
| | ADD: 412/ 414 50 TH ST. UNITS A & B |
| | CONT: BMB SOLUTIONS CORP |
| | TEL: (561)503-1415 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 22/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS INDICATE WORK BEING COMPLETED IN BOTH THE |
| | FRONT AND BACK UNITS, BUT NO ADDRESS IS GIVEN TO THE |
| | BACK UNITS TO BE ABLE TO IDENTIFY THEM. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF WORK |
| | BEING PREFORMED UNDER THIS PERMIT. |
| | 2010 FBC-B 501.2 ADDRESS IDENTIFICATION. |
| | |
| | 2) SHEET A1.2 DESIGGN PARAMETERS AND CODE REFERANCES |
| | BOTH REFERANCE THE 2010 FBC-RESIDENTIAL CODE. PLEASE |
| | NOTE THE RESIDENTIAL CODE IS FOR 1 & 2 FAMILY ONLY. |
| | THIS REVIEW IS BEING COMPLETED UNDER THE 2010 |
| | FBC-BUILDING CODE. OCCUPANCY R2. |
| | |
| | 3A) SHEET A1.1 IT APPEARS THAT THE WINDOWS AND DOORS |
| | ARE BEING REPLACED WITHIN 10 FEET OF THE STAIR AND |
| | LANDING ON BOTH THE FRONT AND REAR BUILDINGS. IT |
| | APPEARS THAT EACH UPPER APARTMENT IS A SINGLE MEANS OF |
| | EGRESS, NO ELEVATIONS PROVIDED TO VERIFY. SINGLE MEANS |
| | OF EGRESS WILL NEED 1 HOUR FIRE SEPARATION,COMPLY UNDER |
| | SECTION FBC-B 1019.2., FBC-B 1026.6 EXC. # 2 & 2007 |
| | FBC-B COMMENTARY FIGURE 1023.6(1) PROTECTION OF |
| | EXTERIOR STAIRWAYS. DOORS AND WINDOWS WITHIN THE |
| | FOOTPRINT OF THE EXTERIOR STAIR REQUIRE 1 HOUR FIRE |
| | RATING AND WINDOWS AND DOORS WITHIN 10 FT. OF THE |
| | LANDINGS AND STAIR REQUIRE 3/4 HR. OPENING PROTECTIVES. |
| | SHOW THE FULL LENGTH OF THE EXTERIOR STAIR AND LANDINGS |
| | TO DETERMINE WHICH OPENINGS REQUIRE A 1 HOUR FIRE |
| | RATING AND WHICH REQUIRE 3/4 HOUR FIRE RATING. |
| | |
| | 3B) NOTE WINDOWS AND DOORS THAT HAVE 3/4 HR AND OR 1 |
| | HOUR FIRE RATING NORMALLY DO NOT HAVE LARGE MISSILE |
| | RESISTANT TESTING AND STORM SHUTTERS WILL NEED TO BE |
| | INSTALLED ON THESE OPENINGS. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION FOR CODE COMPLIANCE: |
| | |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.2. |
| | |
| | FL BLD CODE 2010 SECTION 107.2.5., |
| | 1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 PROCEDURES: A |
| | COMPLETE INSTALLATION SCHEDULE SUMMARIZING & |
| | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING |
| | REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC., |
| | SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO |
| | FACILITATE PLAN REVIEW AND PERMIT ISSUANCE |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | NOTE THE JELD-WEN DOORS NOT REVIEWEDD BY THE DESIGNER |
| | OF RECORD. |
| | |
| | 5) PLEASE 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS & MULLIONS IDENTIFY WINDOW SIZES, GLAZING |
| | OPTIONS, MULLION IF REINFORCED, OPTIONS FOR ANCHORING |
| | AND PRESSURES. |
| | (E) SHUTTERS |
| | |
| | 6) SHEET A.2 INDICATES NEW FLOORING BUT NO INFORMATION |
| | ON THE 2ND FLOOR INSULATION, PLEASE PROVIDE TESTING FOR |
| | THE FOLLOWING (3) CODE SECTIONS: |
| | 6A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 6C)TYPE III-TYPE V CONSTRUCTION: |
| | 719.2 CONCEALED INSTALLATION. INSULATING MATERIALS, |
| | WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE |
| | OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |