| 2015-06-16 05:17:42 | 1) SHEET A-1 - THE ADDRESS IN THE CENTER OF THE PLANS |
| | REFER TO A LOCATION IN FT. LAUDERDALE. PLACE THE |
| | CORRECT ADDRESS OF THE JOBSITE ON THE PLANS. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 2) SHT. A-1 - DELETE THE REFERENCE TO BROWARD COUNTY |
| | AMENDMENTS IN THE "CODE RESEARCH" HEADING. |
| | 3) THE DRINKING FOUNTAINS IN THE RECEPTION AREA SHOW A |
| | PARALLEL CLEAR FLOOR SPACE. PER THE FACBC SEC.602.2, |
| | "UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT." SHOW THE REQUIRED FORWARD |
| | APPROACH CENTERED ON THE UNIT. |
| | 4) SHT. A-2 - THE WIDTH OF RESTROOM #02 IN THE |
| | RECEPTION AREA IS NOT WIDE ENOUGH. THE MINIMUM WIDTH |
| | WHERE THE PLUMBING FIXTURES ARE ON THE SAME WALL SHALL |
| | BE 85 INCHES IF BUILT PERFECT; 86 INCHES ALLOWS FOR |
| | CONSTRUCTION TOLERANCES. |
| | 5) THE DEMOLITION PLANS (A1.1 ) SHOW AN EXISTING |
| | LAVATORY IN THE TOILET COMPARTMENTS OF BOTH RESTROOMS. |
| | THE BUILDOUT PLANS SHOW THIS LAVATORY BEING REMOVED. |
| | THIS IS REDUCING THE LEVEL OF ACCESSIBILITY AND |
| | VIOLATES SEC.202.3.1. OF THE 2010 FL. ACCESSIBILITY |
| | CODE. REVISE THE PLANS TO SHOW THE LAVATORIES AND |
| | COMPLY WITH 2010 FL. ACCESSIBILITY CODE SEC.604.8.1.6. |
| | 6) THE GRAB BAR HEIGHT SHALL BE MEASURED FROM FINISH |
| | FLOOR TO THE TOP OF THE GRIPPING SURFACE, NOT THE |
| | CENTERLINE AS SHOWN PER THE FAC SEC. 609.4. |
| | 7) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE |
| | DRINKING FOUNTAINS SHOWN IN THE RECEPTION AREA (01). |
| | WPB AMEND. TO FBC SEC. 107.1. |
| | 8) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR |
| | THE TANKLESS WATER HEATER. A COPY OF THE INSTALLATION |
| | MANUAL SHALL BE ONSITE FOR THE INSPECTOR.WPB AMEND. TO |
| | FBC SEC. 107.1. |
| | 9) THE WATER LINE FOR THE COFFEE DISPENSER SHALL BE |
| | PROTECTED AGAINST BACKFLOW PER 2010 FPC SEC. 608.16.10. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |