2015-06-23 15:55:081ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-1: THE O/A DUCT FOR AHU-1B AND AHU-3 IS
 SHOWN TO BE CAPPED OFF ON THE PLAN: PLEASE CORRECT.
 2) M-1: RETURN AIR FROM THE TRAINING ROOM SHALL NOT BE
 TRANSFERRED INTO THE CORRIDOR- SECTION 601.2 FBC-10
 MECHANICAL.
 3) SHOW THE DISCHARGE OR DRAINAGE LOCATION OF THE
 AHU-1D CONDENSATE PIPING- SECTION 307.
  