2015-06-24 19:08:54JOB PERMIT NUMBER: 15051134
 JOB ADDRESS: 2468 METROCENTRE BLVD.
  WEST PALM BEACH, FL
 DATE: JUNE24TH, 2015
  ELECTRICAL PLAN REVIEW COMMENTS
 PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
 THE INTENT OF THIS REVIEW WAS NOT TO GENERATE A PUNCH
 LIST FOR THE DESIGN PROFESSIONAL, THEREFORE IN ADDITION
 TO THE COMMENTS ENTERED BELOW, THE PLANS AND LIGHTING
 SHOULD BE CAREFULLY REVIEWED FOR COMPLIANCE WITH THE
 2010 EDITION OF THE FBC-B; FBC-E AND THE 2008 EDITION
 OF THE NEC PRIOR TO RESUBMITTING. FOR EASE OF REVIEW,
 PLEASE INDICATE THE ENTRY POINTS INTO THE VARIOUS ROOMS
 ON THE LIGHTING PLAN.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 SHEET E-1:
 1. FBC-B ?1006.2 & NEC 210.70 (F) HAVE SPECIFIC
 REQUIREMENTS FOR EMERGENCY ILLUMINATION IN BLDGS. OVER
 75? HIGH. EMERGENCY LIGHTING IS REQUIRED BUT NOT
 LIMITED TO ROOMS 7, 9, & 25.
 2. FBC-E ? 505 HAS AUTOMATIC LIGHTING CONTROL
 REQUIREMENTS WHICH WAS NOT OBSERVED FOR ROOMS 4, 5, 6,
 9, 11, 23, & 24.
 3. FBC-B ? 1011 HAS SPECIFIC REQUIREMENTS FOR EXIT
 LIGHTING WERE FOUND TO BE MISSING, BUT NOT LIMITED TO
 ROOMS 3, & 5
 SHEET E-2
 1. PER NEC 408.4, PROVIDE A PANEL DIRECTORY FOR PANEL A
 2. PER NEC 422.52, ELECTRIC DRINKING FOUNTAINS SHALL BE
 PROTECTED WITH A GFI CIRCUIT. THERE APPEAR TO BE TWO
 DRINKING FOUNTAINS, ONE IN THE BREAK ROOM, AND ONE IN
 THE RECEPTION AREA.
 3. PER NEC 210.8(B) EVERY OUTLET WITHIN 6? FROM THE
 SINK SHALL BE PROTECTED WITH GFI.
  