| 2015-06-24 19:08:54 | JOB PERMIT NUMBER: 15051134 |
| | JOB ADDRESS: 2468 METROCENTRE BLVD. |
| | WEST PALM BEACH, FL |
| | DATE: JUNE24TH, 2015 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. |
| | THE INTENT OF THIS REVIEW WAS NOT TO GENERATE A PUNCH |
| | LIST FOR THE DESIGN PROFESSIONAL, THEREFORE IN ADDITION |
| | TO THE COMMENTS ENTERED BELOW, THE PLANS AND LIGHTING |
| | SHOULD BE CAREFULLY REVIEWED FOR COMPLIANCE WITH THE |
| | 2010 EDITION OF THE FBC-B; FBC-E AND THE 2008 EDITION |
| | OF THE NEC PRIOR TO RESUBMITTING. FOR EASE OF REVIEW, |
| | PLEASE INDICATE THE ENTRY POINTS INTO THE VARIOUS ROOMS |
| | ON THE LIGHTING PLAN. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | SHEET E-1: |
| | 1. FBC-B ?1006.2 & NEC 210.70 (F) HAVE SPECIFIC |
| | REQUIREMENTS FOR EMERGENCY ILLUMINATION IN BLDGS. OVER |
| | 75? HIGH. EMERGENCY LIGHTING IS REQUIRED BUT NOT |
| | LIMITED TO ROOMS 7, 9, & 25. |
| | 2. FBC-E ? 505 HAS AUTOMATIC LIGHTING CONTROL |
| | REQUIREMENTS WHICH WAS NOT OBSERVED FOR ROOMS 4, 5, 6, |
| | 9, 11, 23, & 24. |
| | 3. FBC-B ? 1011 HAS SPECIFIC REQUIREMENTS FOR EXIT |
| | LIGHTING WERE FOUND TO BE MISSING, BUT NOT LIMITED TO |
| | ROOMS 3, & 5 |
| | SHEET E-2 |
| | 1. PER NEC 408.4, PROVIDE A PANEL DIRECTORY FOR PANEL A |
| | 2. PER NEC 422.52, ELECTRIC DRINKING FOUNTAINS SHALL BE |
| | PROTECTED WITH A GFI CIRCUIT. THERE APPEAR TO BE TWO |
| | DRINKING FOUNTAINS, ONE IN THE BREAK ROOM, AND ONE IN |
| | THE RECEPTION AREA. |
| | 3. PER NEC 210.8(B) EVERY OUTLET WITHIN 6? FROM THE |
| | SINK SHALL BE PROTECTED WITH GFI. |
| | |