Plan Review Notes
Plan Review Notes For Permit 15051123
Permit Number 15051123
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-02 11:35:15PROVISO:
  
 GENERAL PURPOSE RECEPTACLES INSTALLED IN THE BATHROOMS,
 KITCHENS, ROOFTOPS, OUTDOORS, WITHIN SIX FEET OF SINKS,
 AT ELECTRIC DRINKING FOUNTAINS, AND VENDING MACHINES
 MUST BE GFCI PROTECTED. NEC 210.8
  
 ORANGE COLOR CODING OF CONDUCTORS IS RESERVED FOR HIGH
 LEG DELTA SYSTEMS ONLY. NEC 110.15
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  
  