2015-05-30 06:13:591) SUBMIT A FLOOR PLAN SHOWING THE LOCATIONS OF ALL THE
 GAS EQUIPMENT. THE FLOOR PLAN CAN BE HAND DRAWN. WPB
 AMEND. TO 2010 FBC SECS. 107.2.1, 107.3.5.1.5.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE
 WITH THE 2010 FUEL GAS CODE SEC.304.1.
 3) ONE SET OF PLANS IS DONE IN PENCIL. PENCILED PLANS
 ARE UNACCEPTABLE AS ITEMS CAN BE CHANGED. MAKE A COPY
 OF THE PLAN FOR SUBMITTAL. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) SUBMIT THE VENTING REQUIRENENTS FROM THE
 INSTALLATION MANUAL TO ENSURE COMPLIANCE WITH FGC
 SEC.305, 502 & 503.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692