| Plan Review Notes For Permit 15051090 |
| Permit Number |
15051090 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-09-14 14:26:28 | SHT. 1 & SHT. 2 OF THE PLANS FROM JASON HANCHUK SHOW A | | | 1 FT. X 1 FT. SUMP IN THE SUNKEN BAR AREA. THE SUMP | | | DETAIL DOES NOT SHOW ANY PIPING TO OR FROM THE SUMP AND | | | ON SHT.3 THERE IS A DRAWING OF A 3 INCH FLOOR DRAIN | | | DISCHARGING TO A SUMP TANK WITH A PUMP.WHAT KIND OF | | | PIPING CONNECTION ARE YOU PUTTING IN THE SUNKEN BAR | | | AREA? IS THE SUMP DRAINING INTO THE PUMP BASIN? NOTHING | | | MATCHES ON THESE PLANS.CLARIFY. | | | | | | I AM CONFUSED AS TO WHAT IS BEING INSTALLED . PLEASE | | | CALL TO DISCUSS OR SET UP AN APPOINTMENT. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|