2015-08-11 08:30:031) SHT. 2 OF 2 OF THE PLANS FROM J.HANCHUK SHOWS A
 3"PVC PIPE WITH A NOTE STATING "SLOPE TO DRYWELL" BUT
 IT IS SHOWN DISCHARGING TO A 150 GALLON TANK, THE
 SUBMITTED SPECS ARE FOR A 41 GALLON TANK. CLARIFY.
 2) SUBMIT TWO COPIES OF THE PUMP SPEC SHEETS, DRYWELL
 SPEC SHEETS, AND THE DRAWINGS FOR THE DRYWELL PIPING.
 WPB AMEND. TO FBC SEC. 107.1.
 3) SHOW THE PIPE SIZES FOR THE VENT AND ALSO FOR THE
 DISCHARGE LINE FROM THE SUMP TO THE DRYWELL AND ALSO
 THE PIPING BETWEEN THE DRYWELLS. WPB AMEND. TO FBC SEC.
 107.2.1.
  
  