2015-08-13 10:25:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 406.8 (B) WET LOCATIONS. OUTDOOR RECEPTACLES ARE
 REQUIRED TO BE WEATHER PROOF.
  
 2) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 3) NEC 680.22 RECEPTACLES ARE REQUIRED TO BE LOCATED
 NOT LESS THAN 6 FT. FROM THE INSIDE POOL WALL.
  
 4) NEC 680.26 BOND ALL METAL PARTS WITHIN 5 FT. OF THE
 INSIDE POOL WALL.
  
 5) FBC-R 303.6 AND 303.6.1 STAIRWAY ILLUMINATION AND
 LIGHT ACTIVATION.
  
  