| Plan Review Notes For Permit 15051090 |
| Permit Number |
15051090 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-13 10:25:38 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NEC 406.8 (B) WET LOCATIONS. OUTDOOR RECEPTACLES ARE | | | REQUIRED TO BE WEATHER PROOF. | | | | | | 2) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE | | | REQUIRED. | | | | | | 3) NEC 680.22 RECEPTACLES ARE REQUIRED TO BE LOCATED | | | NOT LESS THAN 6 FT. FROM THE INSIDE POOL WALL. | | | | | | 4) NEC 680.26 BOND ALL METAL PARTS WITHIN 5 FT. OF THE | | | INSIDE POOL WALL. | | | | | | 5) FBC-R 303.6 AND 303.6.1 STAIRWAY ILLUMINATION AND | | | LIGHT ACTIVATION. | | | | | | |
|