| Plan Review Notes For Permit 15051090 |
| Permit Number |
15051090 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-12 05:51:29 | 1) SHT. 2 OF 2 SHOWS A 3"PVC PIPE WITH A NOTE STATING | | | "SLOPE TO DRYWELL" BUT IT IS SHOWN DISCHARGING TO A 150 | | | GALLON TANK. WHERE IS THIS WATER BEING DISCHARGED? HOW | | | IS THE TANK BEING DRAINED/PUMPED OUT. WHERE IS THE | | | TERMINATION POINT? CLARIFY. | | | 2) SUBMIT 2 COPIES OF MANUFACTURER SPECIFICATION SHEETS | | | AND INSTALLATION INSTRUCTIONS FOR THE TANK. WPB AMEND. | | | TO 2010 FBC SEC. 107.2.1. | | | 3) AN OVERFLOW/RELIEF VENT SHOULD BE PROVIDED ON THIS | | | SYSTEM. WHEN THE TANK FILLS IT WILL BACK UP IN THE BAR | | | AREA CREATING AND UNSANITARY CCONDITION. | | | 4) SHOW THE LOCATION OF THE TANK ON THE SITE PLAN.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|