Plan Review Notes
Plan Review Notes For Permit 15051090
Permit Number 15051090
Review Stop G
Sequence Number 1
Notes
Date Text
2015-06-12 05:52:481) AN APPLICATION FOR GAS INSTALLATION HAS BEEN
 SUBMITTED BUT THERE IS NO GAS WORK SHOWN ON THE PLANS.
 CLARIFY.
 2) SUBMIT A GAS RISER DRAWING FOR REVIEW. WPB AMEND. TO
 FBC SEC. 107.3.5.3.
 3) SUBMIT MANUF. SPECIFICATIONS FOR ALL GAS
 EQUIPMEENT.ALL EQUIPMENT SHALL BE LISTED AND LABELED
 PER 2010 FBC SEC.G2404.3.
 4) SHOW THE LOCATION OF ALL GAS EQUIPMENT/APPLIANCES ON
 THE PLAN. WPB AMEND. TO FBC SEC. 107.3.5.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  