| Plan Review Notes For Permit 15051090 |
| Permit Number |
15051090 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-26 08:40:21 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE FLOOR OF THE SUNKEN BAR IS MORE THAN 30" BELOW | | | GRADE. PROVIDE GUARDS AROUND THE SUNKEN BAR AS REQUIRED | | | BY FBC - R312. | | | | | | 2) PROVIDE A SURVEY/SITE PLAN INDICATING THE LOCATION | | | OF THE POOL AND SUNKEN BAR AREA IN RELATION TO THE | | | STRUCTURES LOCATED ON THE PROPERTY AND PROPERTY LINES. | | | FBC 107.2.1 | | | |
|